Worked example · Controls & protection

Supercritical outlet with adjusted diameter

A steep barrel exits at an estimated 11 in normal flow depth inside a 36 in pipe.

Inputs

Culvert outfall
0–1,500 cfs
6–144 in
0–20 ft
0.1–144 in

For unknown tailwater enter zero. The HEC-14 minimum is applied automatically.

Stone and placement
0–60 in
2–4
40–200 lb/ft³

Use in-place bulk density, including voids, for material tonnage.

Riprap apron plan

Live results
Riprap apron plan Available stone meets D₅₀. Low tailwater (TW < 0.5Dₒ). Example class dimensions use the next qualifying size. REQUIRED D₅₀ 3.97 in APRON LENGTH 12 ft FLARED WIDTH 17 ft PLACED MASS 12.85 US ton Supercritical outletLow tailwaterW₂Lₐ · 12 ft 0Required D₅₀2× required

Available stone meets D₅₀

Low tailwater (TW < 0.5Dₒ). Example class dimensions use the next qualifying size.

Stone sizing uses the minimum tailwater of 0.4 effective diameters.

Calculation results

Required D₅₀
3.97 in
Apron length
12 ft
Flared width
17 ft
Placed mass
12.85 US ton
Example class D₅₀
5 in
Apron thickness
17.5 in
Upstream apron width
9 ft
Placed volume
227.5 ft³
Available stone reserve
2.03 in
Tailwater used
0.78 ft
Effective diameter
1.96 ft
Actual TW / Dₒ
0.217

Worked calculation

The 23.5 in effective diameter changes the stone size, while the apron length and initial width still reference the physical outlet.

D₅₀ = 0.2 D[Q/(√g D⁵ᐟ²)]⁴ᐟ³(D/TW) · W₂ = 3Dₒ + 2Lₐ/3 · mass = placed volume × bulk density.

HEC-14 Eq. 10.4 limits tailwater to 0.4–1.0 effective diameters. USDA classifies site tailwater at 0.5 outlet diameters. For supercritical flow, the effective diameter is the mean of outlet diameter and normal depth. Apron dimensions follow the next qualifying example class in HEC-14 Table 10.1 with a 1:3 flare per side. Larger sizes or tailwater beyond the equation range need site-specific outlet protection analysis.

Open the main calculator