Calculation references
Methodology
Equations, unit conventions and applicability for the eight StormDrainLab worksheets.
Units and interpretation
US customary and SI views preserve each physical input. Manning, gutter and culvert calculations use a consistent customary basis and convert the result to SI. For the Rational Method, SI uses the exact unit conversion and the US view also offers the conventional factor of 1.000.
Default inputs and worked examples are illustrative. Use local rainfall data, approved criteria, surveyed geometry and documented material properties. Review drainage paths, backwater, routing and erosion conditions when a screening result controls a design.
Rational Method
C = Σ(Aᵢ Cᵢ) / ΣAᵢ · Q = C i A × K · t꜀ = 0.0078 L⁰·⁷⁷ S⁻⁰·³⁸⁵ in minutes with L in ft.
The exact US factor is 121/120 and is displayed as 1.0083. SI uses Q = C i A / 360 with i in mm/hr and A in ha. The rounded US convention uses 1.000. Kirpich estimates the channel travel component. Add sheet and shallow concentrated travel where applicable, and verify local minimum durations and area limits.
Curve Number Runoff
S = 1000/CN − 10 (inches) · Iₐ = λS · Qd = (P − Iₐ)²/(P − Iₐ + S) for P > Iₐ, else 0.
The 0.20 option follows TR-55. The 0.05 option evaluates the entered CN values as supplied. For design with 0.05, use curve numbers calibrated to that choice. Weighted CN is evaluated before the nonlinear runoff equation. For strongly mixed or hydraulically disconnected cover, consider separate runoff calculations.
Trapezoidal Swale
A = y(b + zy) · R = A/P · Q = K A R²ᐟ³ S¹ᐟ²/n · Fr = V/√(gA/T) · τavg = γRS.
Assumes steady uniform flow and a straight channel. The comparison uses average boundary shear. The depth-based bed shear is shown separately. HEC-15 lining design also evaluates local maximum shear, bends and steep grades.
Storm Sewer Pipe
θ = 2 acos(1 − 2d/D) · A = D²(θ − sin θ)/8 · P = Dθ/2 · Q = K A R²ᐟ³ S¹ᐟ²/n.
Assumes uniform gravity flow with fixed Manning n and no backwater. At a zero slope the ratios compare section conveyance, while both discharges and velocities are zero. At high part-full depths Q can exceed its full-section reference because hydraulic radius is larger.
Street Gutter Spread
Q = (Kᵤ/n) Sₓ⁵ᐟ³ Sₗ¹ᐟ² T⁸ᐟ³ · d = TSₓ · Eₒ = 1 − (1 − min(W/T, 1))⁸ᐟ³.
Uniform triangular pavement and separate on-grade inlet alternatives. Spread above the curb is outside this model, as are sag flow, depressed gutters, debris, clogging and surcharge. Curb capture uses HEC-22 Equations 7.10 and 7.13. Equation 7.10 can underestimate the required opening length, especially for openings of 10 ft (3.05 m) or more. See FHWA-HRT-22-061 for the alternative method. Results use the published US coefficients and convert to SI.
Detention Pond
Vreq = 60[Qin(tᵈ + t꜀/4) − Qout(tᵈ/2 + 3t꜀/4)] · Full orifice Qor = CᵈA√(2gh) · Qw = CʷLh³ᐟ².
The hydrograph assumes tᵈ ≥ t꜀, a 1.5 t꜀ recession and a linear release rising limb. Storage is set to zero when the allowable rate already meets the inflow peak. Test multiple IDF durations to find the controlling one. The steady-flow rating uses the EPA SWMM equivalent weir for a partly wetted side orifice and centerline head for a full opening. Downstream submergence and dynamic routing require a separate analysis.
Culvert Headwater
HWin from Appendix A · HWout = h₀ + hfriction + (kₑ + 1)V²/(2g) − LS · HW = max(HWin, HWout).
The inlet calculation uses HDS-5 Table A.1. A linear blend between the published branch endpoints is used near inlet submergence. The outlet is a full-barrel energy screen with h₀ = max(TW, (d꜀ + D)/2), capped at D for the starting depth proxy before taking the maximum with tailwater. For outlet headwater below 0.75D, verify with a backwater calculation. The 1.2 ratio is a worksheet criterion. Road overtopping uses the surveyed road crest.
Riprap Scour Apron
D₅₀ = 0.2 D[Q/(√g D⁵ᐟ²)]⁴ᐟ³(D/TW) · W₂ = 3Dₒ + 2Lₐ/3 · mass = placed volume × bulk density.
HEC-14 Eq. 10.4 limits tailwater to 0.4–1.0 effective diameters. USDA classifies site tailwater at 0.5 outlet diameters. For supercritical flow, the effective diameter is the mean of outlet diameter and normal depth. Apron dimensions follow the next qualifying example class in HEC-14 Table 10.1 with a 1:3 flare per side. Larger sizes or tailwater beyond the equation range need site-specific outlet protection analysis.