88% UVT Annular Reactor Dose
Estimate optical dose, exposure and lamp count for a four-lamp reactor at 400 gpm and 88% UVT.
Disinfection
Explore annular UV attenuation, exposure, derated intensity and lamp power. Derive RED from applicable biodosimetry data.
For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.
Estimate optical dose, exposure and lamp count for a four-lamp reactor at 400 gpm and 88% UVT.
Check the Beer–Lambert limiting case at 100% UVT while keeping annular geometry and sleeve derating.
Compare exposure, water attenuation and estimated lamp count for 65% UVT and a 5 cm annular path.
Double flow to 800 gpm while keeping a 32 gal illuminated volume and compare modeled UV dose.
Apply separate 65% sleeve and 60% end-of-life lamp factors to estimate their combined impact on UV dose.
Derive a 42 mJ/cm² reduction equivalent dose from measured log inactivation and a bench dose-response slope.
α = −ln(UVT/100) / 1 cm, I(x)/I₀ = r₀/(r₀+x) × e^(−αx)Use UVT at 254 nm over a 1 cm cell. The model assumes a cylindrical lamp, uniform water and a representative annular gap.
Ī = I₀ × [2r₀/(2r₀+L)] × [1−e^(−αL)]/(αL) × sleeve × EOLL × NThe absorption term tends to one at 100% UVT. Exposure is illuminated volume divided by flow, in seconds. Modeled dose is Ī × exposure in mJ/cm².
Nneeded = ceil(target / dose per lamp), kW = Nneeded × W / 1,000The model holds hydraulic exposure and the independent contribution per lamp fixed. Use clean, new-lamp sleeve-interface intensity before the entered fouling and aging factors.
RED = observed log inactivation / calibrated bench slopeOptional test inputs require a measured reactor challenge result and a log-linear bench curve through the origin over that response range. Use the validated envelope and validation factors for regulatory credit.
The optical estimate assumes uniform axial flow and independent lamp contributions. Short circuiting, lamp arrangement, sensor response and the dose distribution require manufacturer validation. EPA RED comes from biodosimetry.
UVT describes absorption along a water path. Sleeve transmission describes losses across the fouled quartz interface. Lamp aging changes the source output.
Use a full-scale challenge result and the matching bench dose-response curve. The optional RED calculation applies to a through-origin log-linear calibration over the measured response.
WaterTreatLab / Current operating point
US customary units
For engineering planning. Operators must follow site-specific permits, chemical safety data sheets (SDS), manufacturer specifications, and certified regulatory sampling requirements.