WeibullMTBFLab · Engineering calculation
PLC and I/O series critical chain
A PLC, an I/O card and a power supply must all survive. Their MTBFs are 85,000, 120,000 and 60,000 hours.
System survival below single-component reference
Inputs
- Block topology
- Series
- Blocks n
- 3
- Reference component MTBF
- 85,000 h
- Mission age
- 8,760 h
- Individual component MTBFs
- 85,000, 120,000, 60,000 h
Results
- R system
- 72.46555623 %
- F system
- 27.53444377 %
- Survival gain
- -17.74183 pp
- MTTF multiple
- 0.32 ×
- System MTTF
- 27,200 h
- Reference reliability
- 90.20739087 %
- Required active blocks
- 3
- Installed blocks
- 3
Rᵢ(t) = exp(−t / MTBFᵢ)The single-block reference at 8,760 h is 0.90207391.Rsys = ∏ Rᵢ(t)The topology gives Rsys = 0.72465556 and Fsys = 0.27534444.MTTFsys = ∫ Rsys(t) dt over t ≥ 0Mean system life is 27,200 h, or 0.32× reference MTBF.Survival gain = Rsys − RrefThe mission difference is -17.74183 percentage points.
Blocks fail independently. Cold standby uses identical active failure rates, no dormant failures and perfect switching. Common-cause or imperfect switch failures require a separate model.