Industrial automation case

PLC and I/O series critical chain

A PLC, an I/O card and a power supply must all survive. Their MTBFs are 85,000, 120,000 and 60,000 hours.

Inputs

h
h
h
Optional. Enter n values separated by commas.
ReviewSystem survival below single-component reference
R system
72.4656%
F system
27.5344%
Survival gain
-17.7418pp
MTTF multiple
0.32×

System topology and reliability

Reliability block diagram and system versus reference survivalSeries3 of 3 requiredB1B2B3Mission survival0%50%100%05.7e41.1e51.7e5Time (h)SystemReferenceMission

The reference curve represents one component at the entered reference MTBF. Large topologies use representative blocks.

Download

Detailed results

System MTTF
27,200 h
Reference reliability
90.20739087 %
Required active blocks
3
Installed blocks
3

For independent exponential units in series, add the three failure rates to get the system rate.

Formula trace

  1. Rᵢ(t) = exp(−t / MTBFᵢ)The single-block reference at 8,760 h is 0.90207391.
  2. Rsys = ∏ Rᵢ(t)The topology gives Rsys = 0.72465556 and Fsys = 0.27534444.
  3. MTTFsys = ∫ Rsys(t) dt over t ≥ 0Mean system life is 27,200 h, or 0.32× reference MTBF.
  4. Survival gain = Rsys − RrefThe mission difference is -17.74183 percentage points.

Model assumptions

Blocks fail independently. Cold standby uses identical active failure rates, no dormant failures and perfect switching. Common-cause or imperfect switch failures require a separate model.