Industrial automation case

Robot cell redundant safety monitor uptime

Two independently powered diagnostic monitors have different reliability fits. Evaluate the uptime of the monitored channel pair under an either-operates criterion.

Inputs

h
h
h
Optional. Enter n values separated by commas.
PassSystem survival meets single-component reference
R system
96.3226%
F system
3.67737%
Survival gain
18.4425pp
MTTF multiple
1.79605×

System topology and reliability

Reliability block diagram and system versus reference survivalActive parallel1 of 2 requiredB1B2Mission survival0%50%100%02.7e45.3e48e4Time (h)SystemReferenceMission

The reference curve represents one component at the entered reference MTBF. Large topologies use representative blocks.

Download

Detailed results

System MTTF
71,842.11 h
Reference reliability
77.88007831 %
Required active blocks
1
Installed blocks
2

This reliability calculation treats monitor failures as independent. Diagnostic coverage and safety integrity metrics require a separate assessment.

Formula trace

  1. Rᵢ(t) = exp(−t / MTBFᵢ)The single-block reference at 10,000 h is 0.77880078.
  2. Rsys = 1 − ∏ (1−Rᵢ(t))The topology gives Rsys = 0.96322628 and Fsys = 0.03677372.
  3. MTTFsys = ∫ Rsys(t) dt over t ≥ 0Mean system life is 71,842.11 h, or 1.796053× reference MTBF.
  4. Survival gain = Rsys − RrefThe mission difference is 18.44255 percentage points.

Model assumptions

Blocks fail independently. Cold standby uses identical active failure rates, no dormant failures and perfect switching. Common-cause or imperfect switch failures require a separate model.

Method and sources