WeibullMTBFLab · Engineering calculation
Server PSU 1-out-of-2 active redundancy
Two power supplies operate actively. Either can carry the load for a 12,000-hour mission with independent, constant hazards.
System survival meets single-component reference
Inputs
- Block topology
- Active parallel
- Blocks n
- 2
- Reference component MTBF
- 200,000 h
- Mission age
- 12,000 h
Results
- R system
- 99.66086305 %
- F system
- 0.33913695 %
- Survival gain
- 5.48441 pp
- MTTF multiple
- 1.5 ×
- System MTTF
- 300,000 h
- Reference reliability
- 94.17645336 %
- Required active blocks
- 1
- Installed blocks
- 2
Rᵢ(t) = exp(−t / MTBFᵢ)The single-block reference at 12,000 h is 0.94176453.Rsys = 1 − ∏ (1−Rᵢ(t))The topology gives Rsys = 0.99660863 and Fsys = 0.00339137.MTTFsys = ∫ Rsys(t) dt over t ≥ 0Mean system life is 300,000 h, or 1.5× reference MTBF.Survival gain = Rsys − RrefThe mission difference is 5.48441 percentage points.
Blocks fail independently. Cold standby uses identical active failure rates, no dormant failures and perfect switching. Common-cause or imperfect switch failures require a separate model.