Worked example
Metric runoff and RCP sizing for an industrial lot
A 2.1 ha industrial lot has 78% hard cover. The concrete barrel screen uses 82 mm/h rainfall, a 0.8% slope and n = 0.013.
Estimate
Estimated peak runoff
- The barrel screen assumes steady full flow. A culvert design also checks inlet control, tailwater, headwater, debris and outlet conditions.
- Peak runoff · equivalent
- 13.591 ft³/s
- Peak runoff · US gallons
- 6,100.3 US gpm
- Composite runoff coefficient
- 0.805
- Preliminary nominal pipe
- 533.4 mm
- Theoretical full-flow diameter
- 525.11 mm
- Selected barrel capacity
- 0.4013 m³/s
- Full-flow velocity
- 1.796 m/s
- Peak flow ÷ full area
- 1.722 m/s
Download
Working this example
Starting estimate 0.3849 m³/sEstimated peak runoff
Verify the selected reinforced concrete pipe’s actual internal diameter and the next locally stocked size.
Questions & answers
What metric factor turns hectares and millimeters per hour into cubic meters per second?
One hectare receives 10 m³/h per mm/h of rain. Divide by 3,600 seconds per hour, giving Q = C × i × A ÷ 360.
Does the metric RCP size label mean the inside diameter is exact?
It shows the metric equivalent of a nominal size in the screening table. Confirm the manufacturer’s actual inside diameter.