ConcreteEarthLab

Worked example

Runoff from a mixed parking and lawn catchment

A 3.4 ac catchment is 62% paved or roofed. The rest is lawn. A smooth HDPE barrel at 1.25% is screened against the estimated peak.

Inputs

Measurement system
ac
%
in/h
Use local intensity for the design return period and time of concentration.
%
CATCHMENT TO CULVERTIllustrative runoff path to a circular culvert. Pipe capacity is screened at full flow. CATCHMENT TO CULVERT C 0.677 · 3.4 acØ 18 in · slope 1.25%Peak 8.817 ft³/s

Estimate

Estimated peak runoff
8.8171 ft³/s
  • The barrel screen assumes steady full flow. A culvert design also checks inlet control, tailwater, headwater, debris and outlet conditions.
Peak runoff · US gallons
3,957.4 US gpm
Composite runoff coefficient
0.677
Preliminary nominal pipe
18 in
Theoretical full-flow diameter
15.69 in
Selected barrel capacity
12.7222 ft³/s
Full-flow velocity
7.199 ft/s
Peak flow ÷ full area
4.989 ft/s
Download

Working this example

Starting estimate 8.8171 ft³/sEstimated peak runoff

Use the drainage area reaching the inlet and confirm where roof drains actually discharge. Check inlet and outlet control separately.

See the calculator formulas and assumptions

Questions & answers

What composite C comes from 62% hard cover and the remaining lawn?

0.62 × 0.92 + 0.38 × 0.28 gives a composite runoff coefficient of 0.6768.

Why use a local intensity for this parking catchment?

Local intensity varies with return period, storm duration and location. Use the criteria for this inlet and its tributary area.