ICCP Groundbed Resistance Calculator
Estimate vertical or horizontal groundbed resistance, mutual interference and operating voltage drop with optional coke backfill.
Inputs
SI unitsUse surrounding soil resistivity. For low-resistance coke backfill, the optional effective diameter is the column outside diameter.
- Groundbed
- 0.895 Ω
- Single anode
- 7.022 Ω
- Crowding
- 1.53 ×
- Bed drop
- 16.12 V
Anode field and interaction
SchematicVerify field resistivity, backfill contact and actual current distribution before sizing a rectifier.
Calculation details
- Effective anode diameter
- 0.18 m
- Ideal parallel resistance
- 0.5851 Ω
- Mutual resistance term
- 0.3101 Ω
- Total modeled resistance
- 0.8953 Ω
- Target minus modeled resistance
- 0.1047 Ω
- Ideal-parallel efficiency
- 65.36 %
Inputs used
- Groundbed layout
- Vertical shallow row
- Soil resistivity
- 34 Ω·m
- Effective length
- 3 m
- Bare anode diameter
- 0.075 m
- Coke column diameter
- 0.18 m
- Anodes in parallel
- 12
- Center spacing
- 6 m
- Design current
- 18 A
- Resistance target
- 1 Ω
Method and limits
Estimate a single anode
For a shallow vertical electrode, R = ρ[ln(8L/d) − 1]/(2πL). Use the conductive coke column diameter and length when it functions as an equivalent electrode.
Apply trench depth if horizontal
With centerline depth h, set s = 2h and q = √(s² + L²). Dwight’s horizontal bracket is ln[4L(L + q)/(d × s)] + (s − q)/L − 1. Multiply by ρ/(2πL).
Estimate row interaction
With N > 1, add ρ × ln(0.656N)/(πNS) to R_single/N for center spacing S. This Sunde term is for a vertical row. Applying it to parallel horizontal trenches is an approximation. The voltage drop is design current × modeled bed resistance.