Direct-to-chip CDU coolant flow calculator

Size secondary coolant flow, temperature rise and residual air cooling for high-density GPU racks, including 40–150 kW/rack designs.

Engineering schematic

Secondary coolant loop

Live
Secondary coolant loop CDU FLOW 460.7 L/min. LOOP ΔT 10 K. AIR LOAD 80 kW. PUMP INPUT 1.06 kW. See the results table for the full readout. CDU FLOW460.7L/minLOOP ΔT10KAIR LOAD80kWPUMP INPUT1.06kW CDUWaterIT racks25 °C supply35 °C returnAir path80 kW80% to liquid4 racks on loopCDU flow / rated flow0%77% usedLimit 100%

CDU flow headroom 139.3 L/min

Inputs

Rack heat load
kW
%
Secondary coolant loop

Use loop pressure drop at the estimated operating flow.

°C
°C
L/min
kPa
%

Calculation details

MeasureValue
Total rack heat400 kW
Heat captured by coolant320 kW
Residual air cooling load80 kW
Coolant temperature rise10 K
Coolant specific heat4.18 kJ/(kg·K)
Coolant density997 kg/m³
Coolant mass flow7.656 kg/s
Required secondary CDU flow460.71 L/min
Coolant flow per rack115.18 L/min
Rated flow headroom139.29 L/min
Pump hydraulic power0.691 kW
Estimated pump & drive input1.063 kW

Calculation method

  • Qliquid = Prack × rack count × capture fraction
  • Mass flow = Qliquid ÷ (cp × ΔT)
  • Hydraulic kW = ΔP (kPa) × volume flow (m³/s)

The balance uses the supply-to-return temperature rise across the rack loop. Screening properties near room temperature are 4.18 kJ/(kg·K) and 997 kg/m³ for water, and 3.90 kJ/(kg·K) and 1,022 kg/m³ for an approximate 25% propylene glycol mix.

Engineering limits

Confirm coolant properties at the mean loop temperature using your fluid supplier’s data. Use the CDU and cold-plate pressure-drop curves to determine the actual operating point and confirm minimum flow, material compatibility and temperature limits.