100 kW racks using PG25
A four-rack row uses a propylene glycol blend and a 10 K loop rise. It keeps the same nominal CDU as the water baseline.
Engineering schematic
Secondary coolant loop
CDU flow headroom 118.3 L/min
Inputs
Calculation details
| Measure | Value |
|---|---|
| Total rack heat | 400 kW |
| Heat captured by coolant | 320 kW |
| Residual air cooling load | 80 kW |
| Coolant temperature rise | 10 K |
| Coolant specific heat | 3.9 kJ/(kg·K) |
| Coolant density | 1,022 kg/m³ |
| Coolant mass flow | 8.205 kg/s |
| Required secondary CDU flow | 481.71 L/min |
| Coolant flow per rack | 120.43 L/min |
| Rated flow headroom | 118.29 L/min |
| Pump hydraulic power | 0.723 kW |
| Estimated pump & drive input | 1.112 kW |
Update the highlighted inputs to see the results.
Starting calculation
- Multiply 400 kW of rack heat by 80% capture to get 320 kW on the liquid loop.
- Divide captured heat by 3.9 kJ/(kg·K) and a 10 K rise. This gives 8.205 kg/s, or 481.71 L/min at the selected fluid density.
Switch the coolant to water while holding the temperature rise fixed. The volumetric heat capacity determines the flow change.
Calculation method
- Qliquid = Prack × rack count × capture fraction
- Mass flow = Qliquid ÷ (cp × ΔT)
- Hydraulic kW = ΔP (kPa) × volume flow (m³/s)
The balance uses the supply-to-return temperature rise across the rack loop. Screening properties near room temperature are 4.18 kJ/(kg·K) and 997 kg/m³ for water, and 3.90 kJ/(kg·K) and 1,022 kg/m³ for an approximate 25% propylene glycol mix.
Engineering limits
Confirm coolant properties at the mean loop temperature using your fluid supplier’s data. Use the CDU and cold-plate pressure-drop curves to determine the actual operating point and confirm minimum flow, material compatibility and temperature limits.
Related worked examples
DataCenterPUELab · Calculation sheet
100 kW racks using PG25
CDU flow headroom 118.3 L/min
Inputs
- IT load per rack
- 100 kW
- Racks on this CDU
- 4
- Liquid heat capture
- 80 %
- Secondary coolant
- PG25 (25% glycol)
- Supply temperature
- 25 °C
- Return temperature
- 35 °C
- Rated CDU flow
- 600 L/min
- Loop pressure drop
- 90 kPa
- Pump & drive efficiency
- 65 %
Results
- Total rack heat
- 400 kW
- Heat captured by coolant
- 320 kW
- Residual air cooling load
- 80 kW
- Coolant temperature rise
- 10 K
- Coolant specific heat
- 3.9 kJ/(kg·K)
- Coolant density
- 1,022 kg/m³
- Coolant mass flow
- 8.205 kg/s
- Required secondary CDU flow
- 481.71 L/min
- Coolant flow per rack
- 120.43 L/min
- Rated flow headroom
- 118.29 L/min
- Pump hydraulic power
- 0.723 kW
- Estimated pump & drive input
- 1.112 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.