Low ΔT overloads a CDU

The rack row has a 5 K water rise and a 600 L/min CDU. Review whether its pump and flow rating cover the load.

Engineering schematic

Secondary coolant loop

Live
Secondary coolant loop CDU FLOW 967.5 L/min. LOOP ΔT 5 K. AIR LOAD 84 kW. PUMP INPUT 3.42 kW. See the results table for the full readout. CDU FLOW967.5L/minLOOP ΔT5KAIR LOAD84kWPUMP INPUT3.42kW CDUWaterIT racks26 °C supply31 °C returnAir path84 kW80% to liquid4 racks on loopCDU flow / rated flow0%161% usedLimit 100%

CDU flow headroom -367.5 L/min

Inputs

Rack heat load
kW
%
Secondary coolant loop

Use loop pressure drop at the estimated operating flow.

°C
°C
L/min
kPa
%

Calculation details

MeasureValue
Total rack heat420 kW
Heat captured by coolant336 kW
Residual air cooling load84 kW
Coolant temperature rise5 K
Coolant specific heat4.18 kJ/(kg·K)
Coolant density997 kg/m³
Coolant mass flow16.077 kg/s
Required secondary CDU flow967.5 L/min
Coolant flow per rack241.87 L/min
Rated flow headroom-367.5 L/min
Pump hydraulic power2.225 kW
Estimated pump & drive input3.423 kW

Starting calculation

  1. Multiply 420 kW of rack heat by 80% capture to get 336 kW on the liquid loop.
  2. Divide captured heat by 4.18 kJ/(kg·K) and a 5 K rise. This gives 16.077 kg/s, or 967.5 L/min at the selected fluid density.

Increase the return temperature within equipment limits. This model reduces required flow in inverse proportion to the rise.

Calculation method

  • Qliquid = Prack × rack count × capture fraction
  • Mass flow = Qliquid ÷ (cp × ΔT)
  • Hydraulic kW = ΔP (kPa) × volume flow (m³/s)

The balance uses the supply-to-return temperature rise across the rack loop. Screening properties near room temperature are 4.18 kJ/(kg·K) and 997 kg/m³ for water, and 3.90 kJ/(kg·K) and 1,022 kg/m³ for an approximate 25% propylene glycol mix.

Engineering limits

Confirm coolant properties at the mean loop temperature using your fluid supplier’s data. Use the CDU and cold-plate pressure-drop curves to determine the actual operating point and confirm minimum flow, material compatibility and temperature limits.