Single-rack glycol pump input

One 85 kW rack is fed by a glycol loop with a 170 kPa pressure drop and 55% combined pump efficiency.

Engineering schematic

Secondary coolant loop

Live
Secondary coolant loop CDU FLOW 104.9 L/min. LOOP ΔT 10 K. AIR LOAD 15.3 kW. PUMP INPUT 0.54 kW. See the results table for the full readout. CDU FLOW104.9L/minLOOP ΔT10KAIR LOAD15.3kWPUMP INPUT0.54kW CDUPG25IT racks27 °C supply37 °C returnAir path15.3 kW82% to liquid1 rack on loopCDU flow / rated flow0%87% usedLimit 100%

CDU flow headroom 15.1 L/min

Inputs

Rack heat load
kW
%
Secondary coolant loop

Use loop pressure drop at the estimated operating flow.

°C
°C
L/min
kPa
%

Calculation details

MeasureValue
Total rack heat85 kW
Heat captured by coolant69.7 kW
Residual air cooling load15.3 kW
Coolant temperature rise10 K
Coolant specific heat3.9 kJ/(kg·K)
Coolant density1,022 kg/m³
Coolant mass flow1.787 kg/s
Required secondary CDU flow104.92 L/min
Coolant flow per rack104.92 L/min
Rated flow headroom15.08 L/min
Pump hydraulic power0.297 kW
Estimated pump & drive input0.541 kW

Starting calculation

  1. Multiply 85 kW of rack heat by 82% capture to get 69.7 kW on the liquid loop.
  2. Divide captured heat by 3.9 kJ/(kg·K) and a 10 K rise. This gives 1.787 kg/s, or 104.92 L/min at the selected fluid density.

Compare hydraulic power with the estimated pump input. The difference is associated with pump and drive losses.

Calculation method

  • Qliquid = Prack × rack count × capture fraction
  • Mass flow = Qliquid ÷ (cp × ΔT)
  • Hydraulic kW = ΔP (kPa) × volume flow (m³/s)

The balance uses the supply-to-return temperature rise across the rack loop. Screening properties near room temperature are 4.18 kJ/(kg·K) and 997 kg/m³ for water, and 3.90 kJ/(kg·K) and 1,022 kg/m³ for an approximate 25% propylene glycol mix.

Engineering limits

Confirm coolant properties at the mean loop temperature using your fluid supplier’s data. Use the CDU and cold-plate pressure-drop curves to determine the actual operating point and confirm minimum flow, material compatibility and temperature limits.