40 kW rack on a water loop
Two 40 kW racks share a small CDU with 70% of their heat captured by water and a 10 K loop rise.
Engineering schematic
Secondary coolant loop
CDU flow headroom 24.4 L/min
Inputs
Calculation details
| Measure | Value |
|---|---|
| Total rack heat | 80 kW |
| Heat captured by coolant | 56 kW |
| Residual air cooling load | 24 kW |
| Coolant temperature rise | 10 K |
| Coolant specific heat | 4.18 kJ/(kg·K) |
| Coolant density | 997 kg/m³ |
| Coolant mass flow | 1.34 kg/s |
| Required secondary CDU flow | 80.62 L/min |
| Coolant flow per rack | 40.31 L/min |
| Rated flow headroom | 24.38 L/min |
| Pump hydraulic power | 0.07 kW |
| Estimated pump & drive input | 0.107 kW |
Update the highlighted inputs to see the results.
Starting calculation
- Multiply 80 kW of rack heat by 70% capture to get 56 kW on the liquid loop.
- Divide captured heat by 4.18 kJ/(kg·K) and a 10 K rise. This gives 1.34 kg/s, or 80.62 L/min at the selected fluid density.
Include the residual air load in the room cooling schedule. The CDU flow addresses the captured heat.
Calculation method
- Qliquid = Prack × rack count × capture fraction
- Mass flow = Qliquid ÷ (cp × ΔT)
- Hydraulic kW = ΔP (kPa) × volume flow (m³/s)
The balance uses the supply-to-return temperature rise across the rack loop. Screening properties near room temperature are 4.18 kJ/(kg·K) and 997 kg/m³ for water, and 3.90 kJ/(kg·K) and 1,022 kg/m³ for an approximate 25% propylene glycol mix.
Engineering limits
Confirm coolant properties at the mean loop temperature using your fluid supplier’s data. Use the CDU and cold-plate pressure-drop curves to determine the actual operating point and confirm minimum flow, material compatibility and temperature limits.
Related worked examples
DataCenterPUELab · Calculation sheet
40 kW rack on a water loop
CDU flow headroom 24.4 L/min
Inputs
- IT load per rack
- 40 kW
- Racks on this CDU
- 2
- Liquid heat capture
- 70 %
- Secondary coolant
- Water
- Supply temperature
- 24 °C
- Return temperature
- 34 °C
- Rated CDU flow
- 105 L/min
- Loop pressure drop
- 52 kPa
- Pump & drive efficiency
- 65 %
Results
- Total rack heat
- 80 kW
- Heat captured by coolant
- 56 kW
- Residual air cooling load
- 24 kW
- Coolant temperature rise
- 10 K
- Coolant specific heat
- 4.18 kJ/(kg·K)
- Coolant density
- 997 kg/m³
- Coolant mass flow
- 1.34 kg/s
- Required secondary CDU flow
- 80.62 L/min
- Coolant flow per rack
- 40.31 L/min
- Rated flow headroom
- 24.38 L/min
- Pump hydraulic power
- 0.07 kW
- Estimated pump & drive input
- 0.107 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.