100 kW racks using PG25

A four-rack row uses a propylene glycol blend and a 10 K loop rise. It keeps the same nominal CDU as the water baseline.

Engineering schematic

Secondary coolant loop

Live
Secondary coolant loop CDU FLOW 481.7 L/min. LOOP ΔT 10 K. AIR LOAD 80 kW. PUMP INPUT 1.11 kW. See the results table for the full readout. CDU FLOW481.7L/minLOOP ΔT10KAIR LOAD80kWPUMP INPUT1.11kW CDUPG25IT racks25 °C supply35 °C returnAir path80 kW80% to liquid4 racks on loopCDU flow / rated flow0%80% usedLimit 100%

CDU flow headroom 118.3 L/min

Inputs

Rack heat load
kW
%
Secondary coolant loop

Use loop pressure drop at the estimated operating flow.

°C
°C
L/min
kPa
%

Calculation details

MeasureValue
Total rack heat400 kW
Heat captured by coolant320 kW
Residual air cooling load80 kW
Coolant temperature rise10 K
Coolant specific heat3.9 kJ/(kg·K)
Coolant density1,022 kg/m³
Coolant mass flow8.205 kg/s
Required secondary CDU flow481.71 L/min
Coolant flow per rack120.43 L/min
Rated flow headroom118.29 L/min
Pump hydraulic power0.723 kW
Estimated pump & drive input1.112 kW

Starting calculation

  1. Multiply 400 kW of rack heat by 80% capture to get 320 kW on the liquid loop.
  2. Divide captured heat by 3.9 kJ/(kg·K) and a 10 K rise. This gives 8.205 kg/s, or 481.71 L/min at the selected fluid density.

Switch the coolant to water while holding the temperature rise fixed. The volumetric heat capacity determines the flow change.

Calculation method

  • Qliquid = Prack × rack count × capture fraction
  • Mass flow = Qliquid ÷ (cp × ΔT)
  • Hydraulic kW = ΔP (kPa) × volume flow (m³/s)

The balance uses the supply-to-return temperature rise across the rack loop. Screening properties near room temperature are 4.18 kJ/(kg·K) and 997 kg/m³ for water, and 3.90 kJ/(kg·K) and 1,022 kg/m³ for an approximate 25% propylene glycol mix.

Engineering limits

Confirm coolant properties at the mean loop temperature using your fluid supplier’s data. Use the CDU and cold-plate pressure-drop curves to determine the actual operating point and confirm minimum flow, material compatibility and temperature limits.