A low-density rack has two 24-inch perforated tiles and 12.5 Pa of measured static pressure.

Engineering schematic

Underfloor plenum & rack

Live
Underfloor plenum & rack TILE FLOW 0.23 m³/s. OPEN AREA 25 %. STATIC ΔP 12.5 Pa. RACK LIMIT 6.1 kW. See the results table for the full readout. TILE FLOW0.23m³/sOPEN AREA25%STATIC ΔP12.5PaRACK LIMIT6.1kW Cold aisle0.23 m³/sIT rackRaised-floor plenum12.5 Pa2 installed · 2 requiredRack demand / delivered cooling0%82% usedLimit 100%

Rack load headroom 1.1 kW

Inputs

Tile and underfloor plenum
mm
mm
Pa
kg/m³
Air delivery to rack

The delivery fraction accounts for supply air that escapes the rack inlet.

kW
K
%

Calculation details

MeasureValue
Open area per tile0.0929 m²
Gross discharge per tile0.263 m³/s
Delivered airflow per tile0.229 m³/s
Delivered airflow across installed tiles0.457 m³/s
Airflow required at rack load0.377 m³/s
Minimum tiles per rack2 tiles
Maximum rack load at target ΔT6.07 kW
Rack load headroom1.07 kW

Starting calculation

  1. The tile opening is 0.0929 m². Apply its discharge coefficient at 12.5 Pa to obtain 0.263 m³/s gross per tile.
  2. After air delivery losses, one tile supplies 0.229 m³/s. Round the rack’s 0.377 m³/s requirement up to 2 tiles.

Compare raw airflow per tile and useful airflow. Only the delivered portion serves the rack.

Calculation method

  • Aopen = width × depth × open fraction
  • Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
  • Supported rack kW = useful rack airflow × ρ × cp × ΔT

The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.

Engineering limits

Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.