25% tile at a low plenum pressure
A low-density rack has two 24-inch perforated tiles and 12.5 Pa of measured static pressure.
Engineering schematic
Underfloor plenum & rack
Rack load headroom 1.1 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Open area per tile | 0.0929 m² |
| Gross discharge per tile | 0.263 m³/s |
| Delivered airflow per tile | 0.229 m³/s |
| Delivered airflow across installed tiles | 0.457 m³/s |
| Airflow required at rack load | 0.377 m³/s |
| Minimum tiles per rack | 2 tiles |
| Maximum rack load at target ΔT | 6.07 kW |
| Rack load headroom | 1.07 kW |
Update the highlighted inputs to see the results.
Starting calculation
- The tile opening is 0.0929 m². Apply its discharge coefficient at 12.5 Pa to obtain 0.263 m³/s gross per tile.
- After air delivery losses, one tile supplies 0.229 m³/s. Round the rack’s 0.377 m³/s requirement up to 2 tiles.
Compare raw airflow per tile and useful airflow. Only the delivered portion serves the rack.
Calculation method
- Aopen = width × depth × open fraction
- Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
- Supported rack kW = useful rack airflow × ρ × cp × ΔT
The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.
Engineering limits
Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.
Related worked examples
DataCenterPUELab · Calculation sheet
25% tile at a low plenum pressure
Rack load headroom 1.1 kW
Inputs
- Open area
- 25% perforated
- Tile width
- 609.6 mm
- Tile depth
- 609.6 mm
- Plenum static pressure
- 12.5 Pa
- Discharge coefficient
- 0.62
- Air density
- 1.2 kg/m³
- Rack IT load
- 5 kW
- Target rack ΔT
- 11 K
- Tiles serving this rack
- 2
- Air reaching the rack
- 87 %
Results
- Open area per tile
- 0.0929 m²
- Gross discharge per tile
- 0.263 m³/s
- Delivered airflow per tile
- 0.229 m³/s
- Delivered airflow across installed tiles
- 0.457 m³/s
- Airflow required at rack load
- 0.377 m³/s
- Minimum tiles per rack
- 2 tiles
- Maximum rack load at target ΔT
- 6.07 kW
- Rack load headroom
- 1.07 kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.