2N independent power paths

The facility has two identical trains of four modules with only one train needed to carry the design load.

Engineering schematic

A/B capacity topology

Live
A/B capacity topology DESIGN IT 1,632 kW. PATH LIMIT 1,920 kW. REDUNDANT 1,920 kW. STRANDED 288 kW. See the results table for the full readout. DESIGN IT1,632kWPATH LIMIT1,920kWREDUNDANT1,920kWSTRANDED288kW Path A4 × 480 kWPath B4 × 480 kWPlanned IT load1,480 kW85% design capRequired modules onlyPlanned IT / design capacity0%91% usedLimit 100%

Usable IT headroom 152 kW

Inputs

Installed topology

A two-path design uses the same installed module count on each path.

kVA
Design load and cost
%
kW
$

Calculation details

MeasureValue
Real rating per module480 kW
Installed rating per path1,920 kW
Total installed nameplate3,840 kW
Protected capacity before design cap1,920 kW
Capacity on a path with one module removed1,440 kW
Surviving capacity with one full path isolated1,920 kW
Maintenance ceiling with standby reserve held1,920 kW
Usable IT at design cap1,632 kW
Usable capacity assigned to planned load1,480 kW
Capacity allocated to redundancy1,920 kW
Capacity withheld by utilization cap288 kW
Unassigned usable capacity152 kW
Usable IT headroom against plan152 kW
Usable share of installed nameplate42.5 %
Installed module capex576,000 $
Module capex per usable IT kW353 $/kW

Starting calculation

  1. Each 500 kVA module at 0.96 power factor supplies 480 kW. Holding the topology reserve leaves 1,920 kW protected.
  2. Apply the 85% design cap to get 1,632 kW usable. The planned load leaves 152 kW of headroom.

Use cost per usable kW to compare the A/B topology with a single path at the same demand.

Calculation method

  • Module kW = module kVA × rated power factor
  • Protected kW = (modules per path − spare modules) × module kW
  • Design IT limit = protected kW × utilization cap

Dual paths are equal in size and either path can carry the modeled load. The path-isolated ceiling keeps the specified module reserve on the surviving path. Usable capacity is split into assigned load and idle headroom. Stranded kW is the amount withheld by the design cap.

Engineering limits

A single-path design has zero capacity through an isolated path. Module redundancy alone cannot establish a Tier classification. Concurrent maintainability also depends on the physical distribution, isolation, component arrangements and maintenance procedures.