2(N+1) with a surviving-path reserve

Two five-module paths each preserve a standby module. Screen how much protected capacity stays available with one path isolated.

Engineering schematic

A/B capacity topology

Live
A/B capacity topology DESIGN IT 2,280 kW. PATH LIMIT 2,850 kW. REDUNDANT 4,275 kW. STRANDED 570 kW. See the results table for the full readout. DESIGN IT2,280kWPATH LIMIT2,850kWREDUNDANT4,275kWSTRANDED570kW Path A5 × 712.5 kWPath B5 × 712.5 kWPlanned IT load2,100 kW80% design capStandby in each pathPlanned IT / design capacity0%92% usedLimit 100%

Usable IT headroom 180 kW

Inputs

Installed topology

A two-path design uses the same installed module count on each path.

kVA
Design load and cost
%
kW
$

Calculation details

MeasureValue
Real rating per module712.5 kW
Installed rating per path3,562.5 kW
Total installed nameplate7,125 kW
Protected capacity before design cap2,850 kW
Capacity on a path with one module removed2,850 kW
Surviving capacity with one full path isolated3,562.5 kW
Maintenance ceiling with standby reserve held2,850 kW
Usable IT at design cap2,280 kW
Usable capacity assigned to planned load2,100 kW
Capacity allocated to redundancy4,275 kW
Capacity withheld by utilization cap570 kW
Unassigned usable capacity180 kW
Usable IT headroom against plan180 kW
Usable share of installed nameplate32 %
Installed module capex1,100,000 $
Module capex per usable IT kW482 $/kW

Starting calculation

  1. Each 750 kVA module at 0.95 power factor supplies 712.5 kW. Holding the topology reserve leaves 2,850 kW protected.
  2. Apply the 80% design cap to get 2,280 kW usable. The planned load leaves 180 kW of headroom.

Compare raw surviving-path capacity with the more conservative ceiling that holds the configured standby reserve.

Calculation method

  • Module kW = module kVA × rated power factor
  • Protected kW = (modules per path − spare modules) × module kW
  • Design IT limit = protected kW × utilization cap

Dual paths are equal in size and either path can carry the modeled load. The path-isolated ceiling keeps the specified module reserve on the surviving path. Usable capacity is split into assigned load and idle headroom. Stranded kW is the amount withheld by the design cap.

Engineering limits

A single-path design has zero capacity through an isolated path. Module redundancy alone cannot establish a Tier classification. Concurrent maintainability also depends on the physical distribution, isolation, component arrangements and maintenance procedures.