2(N+1) with a surviving-path reserve
Two five-module paths each preserve a standby module. Screen how much protected capacity stays available with one path isolated.
Engineering schematic
A/B capacity topology
Usable IT headroom 180 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Real rating per module | 712.5 kW |
| Installed rating per path | 3,562.5 kW |
| Total installed nameplate | 7,125 kW |
| Protected capacity before design cap | 2,850 kW |
| Capacity on a path with one module removed | 2,850 kW |
| Surviving capacity with one full path isolated | 3,562.5 kW |
| Maintenance ceiling with standby reserve held | 2,850 kW |
| Usable IT at design cap | 2,280 kW |
| Usable capacity assigned to planned load | 2,100 kW |
| Capacity allocated to redundancy | 4,275 kW |
| Capacity withheld by utilization cap | 570 kW |
| Unassigned usable capacity | 180 kW |
| Usable IT headroom against plan | 180 kW |
| Usable share of installed nameplate | 32 % |
| Installed module capex | 1,100,000 $ |
| Module capex per usable IT kW | 482 $/kW |
Update the highlighted inputs to see the results.
Starting calculation
- Each 750 kVA module at 0.95 power factor supplies 712.5 kW. Holding the topology reserve leaves 2,850 kW protected.
- Apply the 80% design cap to get 2,280 kW usable. The planned load leaves 180 kW of headroom.
Compare raw surviving-path capacity with the more conservative ceiling that holds the configured standby reserve.
Calculation method
- Module kW = module kVA × rated power factor
- Protected kW = (modules per path − spare modules) × module kW
- Design IT limit = protected kW × utilization cap
Dual paths are equal in size and either path can carry the modeled load. The path-isolated ceiling keeps the specified module reserve on the surviving path. Usable capacity is split into assigned load and idle headroom. Stranded kW is the amount withheld by the design cap.
Engineering limits
A single-path design has zero capacity through an isolated path. Module redundancy alone cannot establish a Tier classification. Concurrent maintainability also depends on the physical distribution, isolation, component arrangements and maintenance procedures.
Related worked examples
DataCenterPUELab · Calculation sheet
2(N+1) with a surviving-path reserve
Usable IT headroom 180 kW
Inputs
- Redundancy scheme
- 2(N+1)
- Modules per path
- 5
- Rating per module
- 750 kVA
- Rated power factor
- 0.95
- Design utilization cap
- 80 %
- Planned IT load
- 2100 kW
- Installed cost per module
- 110000 $
Results
- Real rating per module
- 712.5 kW
- Installed rating per path
- 3,562.5 kW
- Total installed nameplate
- 7,125 kW
- Protected capacity before design cap
- 2,850 kW
- Capacity on a path with one module removed
- 2,850 kW
- Surviving capacity with one full path isolated
- 3,562.5 kW
- Maintenance ceiling with standby reserve held
- 2,850 kW
- Usable IT at design cap
- 2,280 kW
- Usable capacity assigned to planned load
- 2,100 kW
- Capacity allocated to redundancy
- 4,275 kW
- Capacity withheld by utilization cap
- 570 kW
- Unassigned usable capacity
- 180 kW
- Usable IT headroom against plan
- 180 kW
- Usable share of installed nameplate
- 32 %
- Installed module capex
- 1,100,000 $
- Module capex per usable IT kW
- 482 $/kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.