DataCenterPUELab

N+1 capacity on one UPS path

Five equal 300 kVA modules share one path, including one spare. The plan assigns 850 kW of IT load.

Engineering schematic

A/B capacity topology

Live
A/B capacity topology DESIGN IT 944.6 kW. PATH LIMIT 0 kW. REDUNDANT 288 kW. STRANDED 207.4 kW. See the results table for the full readout. DESIGN IT944.6kWPATH LIMIT0kWREDUNDANT288kWSTRANDED207.4kW Path A5 × 288 kWSingle pathNo B pathPlanned IT load850 kW82% design capStandby in each pathPlanned IT / design capacity0%90% usedLimit 100%

Usable IT headroom 94.6 kW

Inputs

Installed topology

A two-path design uses the same installed module count on each path.

kVA
Design load and cost
%
kW
$

Calculation details

MeasureValue
Real rating per module288 kW
Installed rating per path1,440 kW
Total installed nameplate1,440 kW
Protected capacity before design cap1,152 kW
Capacity on a path with one module removed1,152 kW
Surviving capacity with one full path isolated0 kW
Maintenance ceiling with standby reserve held0 kW
Usable IT at design cap944.64 kW
Usable capacity assigned to planned load850 kW
Capacity allocated to redundancy288 kW
Capacity withheld by utilization cap207.36 kW
Unassigned usable capacity94.64 kW
Usable IT headroom against plan94.64 kW
Usable share of installed nameplate65.6 %
Installed module capex285,000 $
Module capex per usable IT kW302 $/kW

Starting calculation

  1. Each 300 kVA module at 0.96 power factor supplies 288 kW. Holding the topology reserve leaves 1,152 kW protected.
  2. Apply the 82% design cap to get 944.64 kW usable. The planned load leaves 94.64 kW of headroom.

The standby module covers the modeled loss of one module on the same path. Upstream path isolation still leaves zero modeled capacity.

Calculation method

  • Module kW = module kVA × rated power factor
  • Protected kW = (modules per path − spare modules) × module kW
  • Design IT limit = protected kW × utilization cap

Dual paths are equal in size and either path can carry the modeled load. The path-isolated ceiling keeps the specified module reserve on the surviving path. Usable capacity is split into assigned load and idle headroom. Stranded kW is the amount withheld by the design cap.

Engineering limits

A single-path design has zero capacity through an isolated path. Module redundancy alone cannot establish a Tier classification. Concurrent maintainability also depends on the physical distribution, isolation, component arrangements and maintenance procedures.