40% tile retrofit for a denser row

An existing underfloor system has three 40% open tiles at a measured 19 Pa.

Engineering schematic

Underfloor plenum & rack

Live
Underfloor plenum & rack TILE FLOW 0.44 m³/s. OPEN AREA 40 %. STATIC ΔP 19 Pa. RACK LIMIT 18.9 kW. See the results table for the full readout. TILE FLOW0.44m³/sOPEN AREA40%STATIC ΔP19PaRACK LIMIT18.9kW Cold aisle0.44 m³/sIT rackRaised-floor plenum19 Pa3 installed · 3 requiredRack demand / delivered cooling0%74% usedLimit 100%

Rack load headroom 4.9 kW

Inputs

Tile and underfloor plenum
mm
mm
Pa
kg/m³
Air delivery to rack

The delivery fraction accounts for supply air that escapes the rack inlet.

kW
K
%

Calculation details

MeasureValue
Open area per tile0.1486 m²
Gross discharge per tile0.519 m³/s
Delivered airflow per tile0.436 m³/s
Delivered airflow across installed tiles1.307 m³/s
Airflow required at rack load0.966 m³/s
Minimum tiles per rack3 tiles
Maximum rack load at target ΔT18.93 kW
Rack load headroom4.93 kW

Starting calculation

  1. The tile opening is 0.1486 m². Apply its discharge coefficient at 19 Pa to obtain 0.519 m³/s gross per tile.
  2. After air delivery losses, one tile supplies 0.436 m³/s. Round the rack’s 0.966 m³/s requirement up to 3 tiles.

Compare the calculated number of tiles with the floor positions available at the rack front.

Calculation method

  • Aopen = width × depth × open fraction
  • Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
  • Supported rack kW = useful rack airflow × ρ × cp × ΔT

The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.

Engineering limits

Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.

Related worked examples