DataCenterPUELab

415 V balanced A/B whips

Each 32 A whip serves a balanced 7.2 kW. All loads have an independent transfer path.

Engineering schematic

Wye A/B rack distribution

Live
Wye A/B rack distribution LIMIT / LEG 25.6 A. WORST LEG 21.1 A. NEUTRAL MAX 0 A. HEADROOM 4.5 A. See the results table for the full readout. LIMIT / LEG25.6AWORST LEG21.1ANEUTRAL MAX0AHEADROOM4.5A A whipN 0 AB whipN 0 A415/240 V WyeWorst survivorL121.1 AL221.1 AL321.1 ATick = breaker limitWorst surviving phase / continuous limit0%82% usedLimit 100%

Failover breaker headroom 4.5 A

Inputs

Breaker and supply

Enter the share on each phase that has a single cord and no independent transfer path.

A
%
A whip · normal load
kW
kW
kW
B whip · normal load
kW
kW
kW

Calculation details

MeasureValue
Total normal rack load14.4 kW
80% continuous limit per phase25.6 A
Highest phase current after failover21.05 A
Minimum continuous-breaker headroom4.55 A
Highest fundamental neutral current0 A
Balanced real-power limit per whip17.51 kW
A normal · L110.53 A
A normal · L210.53 A
A normal · L310.53 A
B normal · L110.53 A
B normal · L210.53 A
B normal · L310.53 A
A surviving · L121.05 A
A surviving · L221.05 A
A surviving · L321.05 A
B surviving · L121.05 A
B surviving · L221.05 A
B surviving · L321.05 A
A normal · neutral0 A
B normal · neutral0 A
A surviving · neutral0 A
B surviving · neutral0 A
A normal · phase imbalance0 %
B normal · phase imbalance0 %
A surviving · phase imbalance0 %
B surviving · phase imbalance0 %
Rack load shed on loss of A0 kW
Rack load shed on loss of B0 kW

Starting calculation

  1. Multiply the 32 A breaker rating by 0.80 to get 25.6 A continuous per phase.
  2. Convert each phase load at 240 V line-to-neutral and PF 0.95. The highest surviving phase reaches 21.05 A, giving 4.55 A headroom.

Fundamental neutral current is zero for equal phase currents. The surviving phase limit still governs failover.

Calculation method

  • Iphase = 1,000 × kWphase ÷ (VLN × PF)
  • Ineutral = √(Ia² + Ib² + Ic² − IaIb − IbIc − IcIa)
  • Continuous current limit = 0.80 × breaker rating

Use nominal line-to-neutral voltage and phase-to-neutral real kW. Imbalance is largest deviation from the phase mean divided by that mean. Transferable loads from the failed whip are added to corresponding phases on the survivor. Non-transferable single-cord loads on the failed whip drop.

Engineering limits

The neutral model uses fundamental currents with a common power factor and 120° phase spacing. Check harmonic neutral current, conductor ampacity, breaker listing and local code separately. The screen uses 80% of a standard-rated breaker for a continuous load of three hours or more.

Related worked examples