DataCenterPUELab

Recovery with limited charger current

A 25 A charger has limited current available after a 180 kW UPS discharge.

Engineering schematic

DC battery bus & inverter

Live
DC battery bus & inverter RUN TIME 28.6 min. DC DRAW 438.9 A. STRINGS REQ 2. UPS HEAT 7.5 kW. See the results table for the full readout. RUN TIME28.6minDC DRAW438.9ASTRINGS REQ2UPS HEAT7.5kW Battery bank3 strings427.2 VInverterIT load180 kWRecharge path · 25 ATarget runtime / modeled autonomy0%35% usedLimit 100%

Runtime headroom 18.6 min

Inputs

UPS and DC bus
kW
%
V/cell
min
Lead-acid battery bank

Use the charger current available to the battery bank while the UPS serves the load.

Ah
A
%

Calculation details

MeasureValue
Series cells per string240 cells
End-of-discharge bus voltage427.2 V
Inverter DC input187.5 kW
Bank discharge current at cutoff438.9 A
Discharge current per installed string146.3 A
Installed bank capacity at C20390 Ah
Bank C20 reference current19.5 A
Minimum modeled C20 bank capacity162.46 Ah
Parallel strings required for target2 strings
Modeled autonomy at entered load28.6 min
Runtime headroom against target18.6 min
UPS inverter heat7.5 kW
UPS inverter heat25,591 Btu/h
Amp-hours withdrawn in modeled discharge209.22 Ah
Bulk charge time to recover 90% of withdrawn Ah9.41 h

Starting calculation

  1. Multiply 240 cells by 1.78 V to get 427.2 V at cutoff. The inverter draws 438.9 A DC at this voltage.
  2. Apply Peukert’s exponent to 390 Ah of C20 capacity. The model gives 28.6 minutes and requires 2 strings for the target.

Doubling available charge current halves the idealized bulk recovery time at the same charge efficiency.

Calculation method

  • Idc = IT kW × 1,000 ÷ (ηinv × cell count × Vcutoff)
  • Peukert hours = 20 × [(bank C20 ÷ 20) ÷ Idc]ᵏ
  • Charge recovery hours = 0.90 × Ah withdrawn ÷ (charger A × charge efficiency)

The nominal 480 V or 540 V bus uses 240 or 270 nominal 2 V cells in series per string. Current is held at the calculated end-of-discharge value. Runtime is capped at the nominal amp-hour limit at low current. Recharge assumes a constant available charger current during bulk charge.

Engineering limits

Use vendor constant-power discharge tables, temperature and aging corrections, and the full duty cycle for IEEE 485 sizing. The estimate covers lead-acid batteries. Recovery time refers to amp-hours withdrawn in the modeled discharge, with charger taper and float omitted.

Related worked examples