600 mm tile with low-density air

This room uses metric floor tiles and a modestly lower measured air density.

Engineering schematic

Underfloor plenum & rack

Live
Underfloor plenum & rack TILE FLOW 0.48 m³/s. OPEN AREA 40 %. STATIC ΔP 20 Pa. RACK LIMIT 16 kW. See the results table for the full readout. TILE FLOW0.48m³/sOPEN AREA40%STATIC ΔP20PaRACK LIMIT16kW Cold aisle0.48 m³/sIT rackRaised-floor plenum20 Pa3 installed · 2 requiredRack demand / delivered cooling0%62% usedLimit 100%

Rack load headroom 6 kW

Inputs

Tile and underfloor plenum
mm
mm
Pa
kg/m³
Air delivery to rack

The delivery fraction accounts for supply air that escapes the rack inlet.

kW
K
%

Calculation details

MeasureValue
Open area per tile0.144 m²
Gross discharge per tile0.562 m³/s
Delivered airflow per tile0.478 m³/s
Delivered airflow across installed tiles1.433 m³/s
Airflow required at rack load0.895 m³/s
Minimum tiles per rack2 tiles
Maximum rack load at target ΔT16.01 kW
Rack load headroom6.01 kW

Starting calculation

  1. The tile opening is 0.144 m². Apply its discharge coefficient at 20 Pa to obtain 0.562 m³/s gross per tile.
  2. After air delivery losses, one tile supplies 0.478 m³/s. Round the rack’s 0.895 m³/s requirement up to 2 tiles.

Lower density increases orifice volume flow at fixed pressure while reducing the heat carried per unit of volume.

Calculation method

  • Aopen = width × depth × open fraction
  • Qgross = Cd × Aopen × √(2 × ΔP ÷ ρ)
  • Supported rack kW = useful rack airflow × ρ × cp × ΔT

The orifice equation estimates gross flow. Apply the entered delivery fraction for useful rack airflow, then round the required tile count up. Zero pressure gives zero flow and no finite tile count.

Engineering limits

Use the local plenum-to-aisle pressure. Grate geometry, cable congestion and leakage can change the discharge coefficient and pressure distribution. Verify results against the manufacturer’s tile curve and measured air balance.