N+1 capacity on one UPS path
Five equal 300 kVA modules share one path, including one spare. The plan assigns 850 kW of IT load.
Engineering schematic
A/B capacity topology
Usable IT headroom 94.6 kW
Inputs
Calculation details
| Measure | Value |
|---|---|
| Real rating per module | 288 kW |
| Installed rating per path | 1,440 kW |
| Total installed nameplate | 1,440 kW |
| Protected capacity before design cap | 1,152 kW |
| Capacity on a path with one module removed | 1,152 kW |
| Surviving capacity with one full path isolated | 0 kW |
| Maintenance ceiling with standby reserve held | 0 kW |
| Usable IT at design cap | 944.64 kW |
| Usable capacity assigned to planned load | 850 kW |
| Capacity allocated to redundancy | 288 kW |
| Capacity withheld by utilization cap | 207.36 kW |
| Unassigned usable capacity | 94.64 kW |
| Usable IT headroom against plan | 94.64 kW |
| Usable share of installed nameplate | 65.6 % |
| Installed module capex | 285,000 $ |
| Module capex per usable IT kW | 302 $/kW |
Update the highlighted inputs to see the results.
Starting calculation
- Each 300 kVA module at 0.96 power factor supplies 288 kW. Holding the topology reserve leaves 1,152 kW protected.
- Apply the 82% design cap to get 944.64 kW usable. The planned load leaves 94.64 kW of headroom.
The standby module covers the modeled loss of one module on the same path. Upstream path isolation still leaves zero modeled capacity.
Calculation method
- Module kW = module kVA × rated power factor
- Protected kW = (modules per path − spare modules) × module kW
- Design IT limit = protected kW × utilization cap
Dual paths are equal in size and either path can carry the modeled load. The path-isolated ceiling keeps the specified module reserve on the surviving path. Usable capacity is split into assigned load and idle headroom. Stranded kW is the amount withheld by the design cap.
Engineering limits
A single-path design has zero capacity through an isolated path. Module redundancy alone cannot establish a Tier classification. Concurrent maintainability also depends on the physical distribution, isolation, component arrangements and maintenance procedures.
Related worked examples
DataCenterPUELab · Calculation sheet
N+1 capacity on one UPS path
Usable IT headroom 94.6 kW
Inputs
- Redundancy scheme
- N+1
- Modules per path
- 5
- Rating per module
- 300 kVA
- Rated power factor
- 0.96
- Design utilization cap
- 82 %
- Planned IT load
- 850 kW
- Installed cost per module
- 57000 $
Results
- Real rating per module
- 288 kW
- Installed rating per path
- 1,440 kW
- Total installed nameplate
- 1,440 kW
- Protected capacity before design cap
- 1,152 kW
- Capacity on a path with one module removed
- 1,152 kW
- Surviving capacity with one full path isolated
- 0 kW
- Maintenance ceiling with standby reserve held
- 0 kW
- Usable IT at design cap
- 944.64 kW
- Usable capacity assigned to planned load
- 850 kW
- Capacity allocated to redundancy
- 288 kW
- Capacity withheld by utilization cap
- 207.36 kW
- Unassigned usable capacity
- 94.64 kW
- Usable IT headroom against plan
- 94.64 kW
- Usable share of installed nameplate
- 65.6 %
- Installed module capex
- 285,000 $
- Module capex per usable IT kW
- 302 $/kW
Screening estimate. Confirm against facility and manufacturer data for engineering decisions.