N single-path installed capacity

A small room has three required modules and one distribution path. Screen its normal capacity and maintenance exposure.

Engineering schematic

A/B capacity topology

Live
A/B capacity topology DESIGN IT 540 kW. PATH LIMIT 0 kW. REDUNDANT 0 kW. STRANDED 135 kW. See the results table for the full readout. DESIGN IT540kWPATH LIMIT0kWREDUNDANT0kWSTRANDED135kW Path A3 × 225 kWSingle pathNo B pathPlanned IT load480 kW80% design capRequired modules onlyPlanned IT / design capacity0%89% usedLimit 100%

Usable IT headroom 60 kW

Inputs

Installed topology

A two-path design uses the same installed module count on each path.

kVA
Design load and cost
%
kW
$

Calculation details

MeasureValue
Real rating per module225 kW
Installed rating per path675 kW
Total installed nameplate675 kW
Protected capacity before design cap675 kW
Capacity on a path with one module removed450 kW
Surviving capacity with one full path isolated0 kW
Maintenance ceiling with standby reserve held0 kW
Usable IT at design cap540 kW
Usable capacity assigned to planned load480 kW
Capacity allocated to redundancy0 kW
Capacity withheld by utilization cap135 kW
Unassigned usable capacity60 kW
Usable IT headroom against plan60 kW
Usable share of installed nameplate80 %
Installed module capex129,000 $
Module capex per usable IT kW239 $/kW

Starting calculation

  1. Each 250 kVA module at 0.9 power factor supplies 225 kW. Holding the topology reserve leaves 675 kW protected.
  2. Apply the 80% design cap to get 540 kW usable. The planned load leaves 60 kW of headroom.

Compare normal design capacity with the path-isolation row. The single path cannot support the load while isolated.

Calculation method

  • Module kW = module kVA × rated power factor
  • Protected kW = (modules per path − spare modules) × module kW
  • Design IT limit = protected kW × utilization cap

Dual paths are equal in size and either path can carry the modeled load. The path-isolated ceiling keeps the specified module reserve on the surviving path. Usable capacity is split into assigned load and idle headroom. Stranded kW is the amount withheld by the design cap.

Engineering limits

A single-path design has zero capacity through an isolated path. Module redundancy alone cannot establish a Tier classification. Concurrent maintainability also depends on the physical distribution, isolation, component arrangements and maintenance procedures.