DataCenterPUELab

Uneven phase allocation raises neutral demand

Each whip serves the same aggregate kW but the two whips have different phase allocations.

Engineering schematic

Wye A/B rack distribution

Live
Wye A/B rack distribution LIMIT / LEG 25.6 A. WORST LEG 26.3 A. NEUTRAL MAX 15.8 A. HEADROOM -0.7 A. See the results table for the full readout. LIMIT / LEG25.6AWORST LEG26.3ANEUTRAL MAX15.8AHEADROOM-0.7A A whipN 12.2 AB whipN 9.6 A415/240 V WyeWorst survivorL126.3 AL221.9 AL38.8 ATick = breaker limitWorst surviving phase / continuous limit0%103% usedLimit 100%

Failover breaker headroom -0.7 A

Inputs

Breaker and supply

Enter the share on each phase that has a single cord and no independent transfer path.

A
%
A whip · normal load
kW
kW
kW
B whip · normal load
kW
kW
kW

Calculation details

MeasureValue
Total normal rack load13 kW
80% continuous limit per phase25.6 A
Highest phase current after failover26.32 A
Minimum continuous-breaker headroom-0.72 A
Highest fundamental neutral current15.81 A
Balanced real-power limit per whip17.51 kW
A normal · L117.54 A
A normal · L26.58 A
A normal · L34.39 A
B normal · L18.77 A
B normal · L215.35 A
B normal · L34.39 A
A surviving · L126.32 A
A surviving · L221.93 A
A surviving · L38.77 A
B surviving · L126.32 A
B surviving · L221.93 A
B surviving · L38.77 A
A normal · neutral12.21 A
B normal · neutral9.56 A
A surviving · neutral15.81 A
B surviving · neutral15.81 A
A normal · phase imbalance84.62 %
B normal · phase imbalance61.54 %
A surviving · phase imbalance53.85 %
B surviving · phase imbalance53.85 %
Rack load shed on loss of A0 kW
Rack load shed on loss of B0 kW

Starting calculation

  1. Multiply the 32 A breaker rating by 0.80 to get 25.6 A continuous per phase.
  2. Convert each phase load at 240 V line-to-neutral and PF 0.95. The highest surviving phase reaches 26.32 A, giving -0.72 A headroom.

Compare normal neutral currents with the two survivor cases. Different phase distributions change the fundamental vector sum.

Calculation method

  • Iphase = 1,000 × kWphase ÷ (VLN × PF)
  • Ineutral = √(Ia² + Ib² + Ic² − IaIb − IbIc − IcIa)
  • Continuous current limit = 0.80 × breaker rating

Use nominal line-to-neutral voltage and phase-to-neutral real kW. Imbalance is largest deviation from the phase mean divided by that mean. Transferable loads from the failed whip are added to corresponding phases on the survivor. Non-transferable single-cord loads on the failed whip drop.

Engineering limits

The neutral model uses fundamental currents with a common power factor and 120° phase spacing. Check harmonic neutral current, conductor ampacity, breaker listing and local code separately. The screen uses 80% of a standard-rated breaker for a continuous load of three hours or more.

Related worked examples