Single-cord equipment without transfer

One quarter of each whip’s phase load is single-cord equipment without a rack transfer switch.

Engineering schematic

Wye A/B rack distribution

Live
Wye A/B rack distribution LIMIT / LEG 25.6 A. WORST LEG 21.4 A. NEUTRAL MAX 4.6 A. HEADROOM 4.2 A. See the results table for the full readout. LIMIT / LEG25.6AWORST LEG21.4ANEUTRAL MAX4.6AHEADROOM4.2A A whipN 3.4 AB whipN 1.6 A415/240 V WyeWorst survivorL121.4 AL218.2 AL316.1 ATick = breaker limitWorst surviving phase / continuous limit0%84% usedLimit 100%

Failover breaker headroom 4.2 A. Single-cord load drops on a feed loss.

Inputs

Breaker and supply

Enter the share on each phase that has a single cord and no independent transfer path.

A
%
A whip · normal load
kW
kW
kW
B whip · normal load
kW
kW
kW

Calculation details

MeasureValue
Total normal rack load14.4 kW
80% continuous limit per phase25.6 A
Highest phase current after failover21.38 A
Minimum continuous-breaker headroom4.22 A
Highest fundamental neutral current4.59 A
Balanced real-power limit per whip17.51 kW
A normal · L113.16 A
A normal · L210.96 A
A normal · L39.21 A
B normal · L110.96 A
B normal · L29.65 A
B normal · L39.21 A
A surviving · L121.38 A
A surviving · L218.2 A
A surviving · L316.12 A
B surviving · L120.83 A
B surviving · L217.87 A
B surviving · L316.12 A
A normal · neutral3.43 A
B normal · neutral1.58 A
A surviving · neutral4.59 A
B surviving · neutral4.13 A
A normal · phase imbalance18.42 %
B normal · phase imbalance10.29 %
A surviving · phase imbalance15.16 %
B surviving · phase imbalance14 %
Rack load shed on loss of A1.9 kW
Rack load shed on loss of B1.7 kW

Starting calculation

  1. Multiply the 32 A breaker rating by 0.80 to get 25.6 A continuous per phase.
  2. Convert each phase load at 240 V line-to-neutral and PF 0.95. The highest surviving phase reaches 21.38 A, giving 4.22 A headroom.

Electrical headroom and load continuity are separate results. The shed-load rows quantify what goes offline.

Calculation method

  • Iphase = 1,000 × kWphase ÷ (VLN × PF)
  • Ineutral = √(Ia² + Ib² + Ic² − IaIb − IbIc − IcIa)
  • Continuous current limit = 0.80 × breaker rating

Use nominal line-to-neutral voltage and phase-to-neutral real kW. Imbalance is largest deviation from the phase mean divided by that mean. Transferable loads from the failed whip are added to corresponding phases on the survivor. Non-transferable single-cord loads on the failed whip drop.

Engineering limits

The neutral model uses fundamental currents with a common power factor and 120° phase spacing. Check harmonic neutral current, conductor ampacity, breaker listing and local code separately. The screen uses 80% of a standard-rated breaker for a continuous load of three hours or more.