Runtime shortfall on an undersized bank

A future 600 kW UPS load is assessed against a bank of three 120 Ah strings and a 15-minute target.

Engineering schematic

DC battery bus & inverter

Live
DC battery bus & inverter RUN TIME 4.7 min. DC DRAW 1,519.8 A. STRINGS REQ 8. UPS HEAT 38.3 kW. See the results table for the full readout. RUN TIME4.7minDC DRAW1,519.8ASTRINGS REQ8UPS HEAT38.3kW Battery bank3 strings420 VInverterIT load600 kWRecharge path · 125 ATarget runtime / modeled autonomy0%320% usedLimit 100%

Runtime headroom -10.3 min

Inputs

UPS and DC bus
kW
%
V/cell
min
Lead-acid battery bank

Use the charger current available to the battery bank while the UPS serves the load.

Ah
A
%

Calculation details

MeasureValue
Series cells per string240 cells
End-of-discharge bus voltage420 V
Inverter DC input638.3 kW
Bank discharge current at cutoff1,519.76 A
Discharge current per installed string506.59 A
Installed bank capacity at C20360 Ah
Bank C20 reference current18 A
Minimum modeled C20 bank capacity912.71 Ah
Parallel strings required for target8 strings
Modeled autonomy at entered load4.69 min
Runtime headroom against target-10.31 min
UPS inverter heat38.3 kW
UPS inverter heat130,678 Btu/h
Amp-hours withdrawn in modeled discharge118.76 Ah
Bulk charge time to recover 90% of withdrawn Ah1.01 h

Starting calculation

  1. Multiply 240 cells by 1.75 V to get 420 V at cutoff. The inverter draws 1,519.76 A DC at this voltage.
  2. Apply Peukert’s exponent to 360 Ah of C20 capacity. The model gives 4.69 minutes and requires 8 strings for the target.

A negative runtime margin is the modeled time shortfall at the selected load and cutoff voltage.

Calculation method

  • Idc = IT kW × 1,000 ÷ (ηinv × cell count × Vcutoff)
  • Peukert hours = 20 × [(bank C20 ÷ 20) ÷ Idc]ᵏ
  • Charge recovery hours = 0.90 × Ah withdrawn ÷ (charger A × charge efficiency)

The nominal 480 V or 540 V bus uses 240 or 270 nominal 2 V cells in series per string. Current is held at the calculated end-of-discharge value. Runtime is capped at the nominal amp-hour limit at low current. Recharge assumes a constant available charger current during bulk charge.

Engineering limits

Use vendor constant-power discharge tables, temperature and aging corrections, and the full duty cycle for IEEE 485 sizing. The estimate covers lead-acid batteries. Recovery time refers to amp-hours withdrawn in the modeled discharge, with charger taper and float omitted.