GasCompressLab

API 521 · Annexes C and F

Continuous recovery purge flare

A steady purge stream uses the continuous Mach 0.20 target and 1.58 kW/m² receptor screen.

What to check

Compare the proposed tip inside diameter with the minimum diameter for the service target.

Operating readout

Edit inputs ↓
Receptor flux
1.04kW/m²
Tip Mach
0.102
Min. height
15.93m
Flame length
19.33m
Within receptor screening levelsModeled receptor radiation and tip Mach meet the selected limits.
Flare stack elevation and ground radiation zonesFLARE STACK ELEVATIONmWind 4 m/sGROUND PLANkW/m²1.580 m4.730 m9.460 mRECEPTOR LIMIT USED66.1%
Ground zones share the flame center’s ground projection. The point-source center and receptor move with the entered wind and geometry.
Calculated details
Tip gas velocity
37.56m/s
Total heat release
84,861.11kW
Peak ground flux
1.49kW/m²
Flame center downwind shift
7.28m
Flame center above grade
28.53m
Distance from flame center to receptor
34.13m
Service Mach target
0.2
Minimum tip ID for selected Mach
203.96mm
Wind-to-jet velocity ratio
0.106
Downwind extent · 1.58 kW/m²
0m
Downwind extent · 4.73 kW/m²
0m
Downwind extent · 9.46 kW/m²
0m

Operating inputs

Flare duty
kg/h
kg/kmol
MJ/kg
%
0.15–0.30 is an illustrative range. Use tip-specific data.
mm
m
m/s
m
kW/m²
Screening landmarks include 1.58, 4.73 and 9.46 kW/m².
Tip and atmosphere
kPa(a)
°C

Calculation basis

Tip and flame

Use actual flow at the flare tip divided by tip area. The API 521 isothermal Mach screen uses √(ZRₛT). Estimate length using a power-law fit to the Annex C/F reference curve and wind offsets by interpolation of flame distortion.

Radiation and height

Use q = τFQ/(4πD²), with D measured from the wind-shifted flame center. Solve for the minimum stack height at the entered receptor. Ground contours are circles centered on the flame projection. Extents are measured downwind from the stack.