GasCompressLab

API 521 · Annexes C and F

High-wind downwind receptor

A steady 16 m/s wind displaces the point-source center toward a nearby downwind receptor.

What to check

Moving the receptor farther downwind can initially increase exposure if it approaches the projected flame center.

Operating readout

Edit inputs ↓
Receptor flux
8.96kW/m²
Tip Mach
0.12
Min. height
40.41m
Flame length
45.2m
Receptor radiation exceeds limitThe point-source estimate exceeds the selected ground-level limit.
Flare stack elevation and ground radiation zonesFLARE STACK ELEVATIONmWind 16 m/sGROUND PLANkW/m²1.5892.6 m4.7352.6 m9.460 mRECEPTOR LIMIT USED189%
Ground zones share the flame center’s ground projection. The point-source center and receptor move with the entered wind and geometry.
Calculated details
Tip gas velocity
40.05m/s
Total heat release
509,166.67kW
Peak ground flux
8.98kW/m²
Flame center downwind shift
21.37m
Flame center above grade
32.91m
Distance from flame center to receptor
32.94m
Service Mach target
0.5
Minimum tip ID for selected Mach
301.37mm
Wind-to-jet velocity ratio
0.399
Downwind extent · 1.58 kW/m²
92.59m
Downwind extent · 4.73 kW/m²
52.56m
Downwind extent · 9.46 kW/m²
0m

Operating inputs

Flare duty
kg/h
kg/kmol
MJ/kg
%
0.15–0.30 is an illustrative range. Use tip-specific data.
mm
m
m/s
m
kW/m²
Screening landmarks include 1.58, 4.73 and 9.46 kW/m².
Tip and atmosphere
kPa(a)
°C

Calculation basis

Tip and flame

Use actual flow at the flare tip divided by tip area. The API 521 isothermal Mach screen uses √(ZRₛT). Estimate length using a power-law fit to the Annex C/F reference curve and wind offsets by interpolation of flame distortion.

Radiation and height

Use q = τFQ/(4πD²), with D measured from the wind-shifted flame center. Solve for the minimum stack height at the entered receptor. Ground contours are circles centered on the flame projection. Extents are measured downwind from the stack.