GasCompressLab

API 521 · Annexes C and F

Hot low-molecular-weight flare gas

A hot light gas stream expands to a high volumetric exit rate at atmospheric tip pressure.

What to check

Compare exit Mach to the allowed emergency value. The small tip can push the input outside the subsonic model range.

Operating readout

Edit inputs ↓
Receptor flux
0.55kW/m²
Tip Mach
1.003
Min. height
0m
Flame length
39.63m
Outside subsonic flare modelThe tip Mach screen reaches or exceeds unity. Obtain a vendor sonic flare model.
Flare stack elevation and ground radiation zonesFLARE STACK ELEVATIONmWind 8 m/sGROUND PLANkW/m²1.580 m4.730 m9.460 mRECEPTOR LIMIT USED11.7%
Ground zones share the flame center’s ground projection. The point-source center and receptor move with the entered wind and geometry.
Calculated details
Tip gas velocity
557.17m/s
Total heat release
385,722.22kW
Peak ground flux
1.2kW/m²
Flame center downwind shift
2.98m
Flame center above grade
61.84m
Distance from flame center to receptor
91.2m
Service Mach target
0.5
Minimum tip ID for selected Mach
318.71mm
Wind-to-jet velocity ratio
0.014
Downwind extent · 1.58 kW/m²
0m
Downwind extent · 4.73 kW/m²
0m
Downwind extent · 9.46 kW/m²
0m

Operating inputs

Flare duty
kg/h
kg/kmol
MJ/kg
%
0.15–0.30 is an illustrative range. Use tip-specific data.
mm
m
m/s
m
kW/m²
Screening landmarks include 1.58, 4.73 and 9.46 kW/m².
Tip and atmosphere
kPa(a)
°C

Calculation basis

Tip and flame

Use actual flow at the flare tip divided by tip area. The API 521 isothermal Mach screen uses √(ZRₛT). Estimate length using a power-law fit to the Annex C/F reference curve and wind offsets by interpolation of flame distortion.

Radiation and height

Use q = τFQ/(4πD²), with D measured from the wind-shifted flame center. Solve for the minimum stack height at the entered receptor. Ground contours are circles centered on the flame projection. Extents are measured downwind from the stack.

Related worked examples