GlassFacadeLab · Center-of-glass thermal model
Cold-climate triple-argon IGU
Worked example · SI
Pass · The center of glass is at least 2 K above the indoor dew point.
Inputs
- Pane count
- Triple pane
- Outer pane
- 6 mm
- Inner pane
- 6 mm
- Middle pane
- 4 mm
- Unit width
- 1.35 m
- Unit height
- 2.1 m
- Gas fill
- Argon
- Cavity width
- 16 mm
- Outer-facing emissivity ε₁
- 0.05
- Inner-facing emissivity ε₂
- 0.84
- Gas fill
- Argon
- Cavity width
- 16 mm
- Outer-facing emissivity ε₁
- 0.84
- Inner-facing emissivity ε₂
- 0.06
- Indoor air temperature
- 22 °C
- Outdoor air temperature
- -30 °C
- Indoor relative humidity
- 40 %
- Spacer Ψ-edge
- Warm edge · 0.04 SI
- Assembly solar transmittance
- 0.42
- Assembly solar absorptance
- 0.34
- Absorbed heat location
- Outer pane
Results
- Glass U-factor
- 0.787 W/(m²·K)
- Glass SHGC
- 0.432
- Glass surface
- 16.7 °C
- Dew margin
- 8.91 K
- Indoor dew point
- 7.772 °C
- Glass plus linear edge U-factor
- 0.885 W/(m²·K)
- Linear spacer transmittance Ψ
- 0.04 W/(m·K)
- Heat flux toward exterior
- 40.93 W/m²
- Cavity 1 gas conductance
- 1.671 W/(m²·K)
- Cavity 1 radiative conductance
- 0.189 W/(m²·K)
- Cavity 2 gas conductance
- 1.538 W/(m²·K)
- Cavity 2 radiative conductance
- 0.291 W/(m²·K)
Formula trace in SI
Gas and radiation
hgap = Nu·k/d + σεeff(T₁ + T₂)(T₁² + T₂²)
Gap 1: 0.967 conductive × Nu 1.729 + 0.189 radiative W/(m²·K). Gap 2: 1.039 conductive × Nu 1.48 + 0.291 radiative W/(m²·K).
Center and edge heat flow
Uc = 1/ΣR; Uglass+edge = Uc + ΨP/A
ΣR = 1.27 m²·K/W, edge addition 0.097 W/(m²·K).
Solar gain
SHGC = τsolar + αsolar·Rout/Rtotal
Inward absorbed fraction 3.38 %, SHGC 0.432.
Condensation margin
Tsi = Ti − q/hin; ΔTdew = Tsi − Tdp
Magnus dew point 7.772 °C, surface 16.684 °C, margin 8.912 K.