Cold-climate triple-argon IGU

Two Low-E surfaces and argon cavities protect a cold-climate residential facade.

Center-of-glass thermal model

Inputs

Glazing build-up
mm
mm
mm
m
m
Exterior cavity
mm
Interior cavity
mm
Climate and solar data
°C
°C
%

Screening result

The center of glass is at least 2 K above the indoor dew point.

Pass
Glass U-factor
0.787W/(m²·K)
Glass SHGC
0.432
Glass surface
16.7°C
Dew margin
8.91K
Insulating glass section and temperature profileIGU heat and condensation. Glass U-factor 0.787 W/(m²·K). Glass SHGC 0.432. Glass surface 16.7 °C. Dew margin 8.91 K.Insulating glass section3 panes · sealed vertical cavitiesExteriorInteriorTemperature profileOutdoor to room side-30 °C22 °CGlass profileDew 7.8 °CCenter-glass dew margin−5 KDew point+5 K

Calculation details

Indoor dew point
7.772 °C
Glass plus linear edge U-factor
0.885 W/(m²·K)
Linear spacer transmittance Ψ
0.04 W/(m·K)
Heat flux toward exterior
40.93 W/m²
Cavity 1 gas conductance
1.671 W/(m²·K)
Cavity 1 radiative conductance
0.189 W/(m²·K)
Cavity 2 gas conductance
1.538 W/(m²·K)
Cavity 2 radiative conductance
0.291 W/(m²·K)

Formula trace in SI

  1. Gas and radiation

    hgap = Nu·k/d + σεeff(T₁ + T₂)(T₁² + T₂²)

    Gap 1: 0.967 conductive × Nu 1.729 + 0.189 radiative W/(m²·K). Gap 2: 1.039 conductive × Nu 1.48 + 0.291 radiative W/(m²·K).

  2. Center and edge heat flow

    Uc = 1/ΣR; Uglass+edge = Uc + ΨP/A

    ΣR = 1.27 m²·K/W, edge addition 0.097 W/(m²·K).

  3. Solar gain

    SHGC = τsolar + αsolar·Rout/Rtotal

    Inward absorbed fraction 3.38 %, SHGC 0.432.

  4. Condensation margin

    Tsi = Ti − q/hin; ΔTdew = Tsi − Tdp

    Magnus dew point 7.772 °C, surface 16.684 °C, margin 8.912 K.