High-humidity pool glazing

Indoor humidity stays high beside a pool while the outside air falls below freezing.

Center-of-glass thermal model

Inputs

Glazing build-up
mm
mm
m
m
Exterior cavity
mm
Climate and solar data
°C
°C
%

Screening result

The room-side glass is below the indoor dew point.

Fail
Glass U-factor
1.447W/(m²·K)
Glass SHGC
0.497
Glass surface
19.4°C
Dew margin
-2.66K
Insulating glass section and temperature profileIGU heat and condensation. Glass U-factor 1.447 W/(m²·K). Glass SHGC 0.497. Glass surface 19.4 °C. Dew margin -2.66 K.Insulating glass section2 panes · sealed vertical cavitiesExteriorInteriorTemperature profileOutdoor to room side-18 °C28 °CGlass profileDew 22 °CCenter-glass dew margin−5 KDew point+5 K

Calculation details

Indoor dew point
22.015 °C
Glass plus linear edge U-factor
1.62 W/(m²·K)
Linear spacer transmittance Ψ
0.08 W/(m·K)
Heat flux toward exterior
66.57 W/m²
Cavity 1 gas conductance
1.729 W/(m²·K)
Cavity 1 radiative conductance
0.235 W/(m²·K)

Formula trace in SI

  1. Gas and radiation

    hgap = Nu·k/d + σεeff(T₁ + T₂)(T₁² + T₂²)

    Gap 1: 1.371 conductive × Nu 1.261 + 0.235 radiative W/(m²·K).

  2. Center and edge heat flow

    Uc = 1/ΣR; Uglass+edge = Uc + ΨP/A

    ΣR = 0.691 m²·K/W, edge addition 0.173 W/(m²·K).

  3. Solar gain

    SHGC = τsolar + αsolar·Rout/Rtotal

    Inward absorbed fraction 6.22 %, SHGC 0.497.

  4. Condensation margin

    Tsi = Ti − q/hin; ΔTdew = Tsi − Tdp

    Magnus dew point 22.015 °C, surface 19.354 °C, margin -2.661 K.