GlassFacadeLab · Center-of-glass thermal model
Cold-room vision panel
Worked example · SI
Fail · The room-side glass is below the indoor dew point.
Inputs
- Pane count
- Double pane
- Outer pane
- 6 mm
- Inner pane
- 6 mm
- Unit width
- 0.46 m
- Unit height
- 0.74 m
- Gas fill
- Argon
- Cavity width
- 13 mm
- Outer-facing emissivity ε₁
- 0.05
- Inner-facing emissivity ε₂
- 0.84
- Indoor air temperature
- 18 °C
- Outdoor air temperature
- -25 °C
- Indoor relative humidity
- 63 %
- Spacer Ψ-edge
- Warm edge · 0.04 SI
- Assembly solar transmittance
- 0.48
- Assembly solar absorptance
- 0.28
- Absorbed heat location
- Outer pane
Results
- Glass U-factor
- 1.456 W/(m²·K)
- Glass SHGC
- 0.498
- Glass surface
- 9.9 °C
- Dew margin
- -0.98 K
- Indoor dew point
- 10.847 °C
- Glass plus linear edge U-factor
- 1.738 W/(m²·K)
- Linear spacer transmittance Ψ
- 0.04 W/(m·K)
- Heat flux toward exterior
- 62.61 W/m²
- Cavity 1 gas conductance
- 1.766 W/(m²·K)
- Cavity 1 radiative conductance
- 0.214 W/(m²·K)
Formula trace in SI
Gas and radiation
hgap = Nu·k/d + σεeff(T₁ + T₂)(T₁² + T₂²)
Gap 1: 1.233 conductive × Nu 1.433 + 0.214 radiative W/(m²·K).
Center and edge heat flow
Uc = 1/ΣR; Uglass+edge = Uc + ΨP/A
ΣR = 0.687 m²·K/W, edge addition 0.282 W/(m²·K).
Solar gain
SHGC = τsolar + αsolar·Rout/Rtotal
Inward absorbed fraction 6.26 %, SHGC 0.498.
Condensation margin
Tsi = Ti − q/hin; ΔTdew = Tsi − Tdp
Magnus dew point 10.847 °C, surface 9.869 °C, margin -0.978 K.