GlassFacadeLab · Center-of-glass thermal model
IGU U-factor, SHGC and condensation calculator
Calculator scenario · SI
Pass · The center of glass is at least 2 K above the indoor dew point.
Inputs
- Pane count
- Double pane
- Outer pane
- 6 mm
- Inner pane
- 6 mm
- Unit width
- 1.35 m
- Unit height
- 2.1 m
- Gas fill
- Argon
- Cavity width
- 14 mm
- Outer-facing emissivity ε₁
- 0.05
- Inner-facing emissivity ε₂
- 0.84
- Indoor air temperature
- 21 °C
- Outdoor air temperature
- -12 °C
- Indoor relative humidity
- 50 %
- Spacer Ψ-edge
- Warm edge · 0.04 SI
- Assembly solar transmittance
- 0.48
- Assembly solar absorptance
- 0.28
- Absorbed heat location
- Outer pane
Results
- Glass U-factor
- 1.36 W/(m²·K)
- Glass SHGC
- 0.496
- Glass surface
- 15.2 °C
- Dew margin
- 5 K
- Indoor dew point
- 10.175 °C
- Glass plus linear edge U-factor
- 1.457 W/(m²·K)
- Linear spacer transmittance Ψ
- 0.04 W/(m·K)
- Heat flux toward exterior
- 44.88 W/m²
- Cavity 1 gas conductance
- 1.571 W/(m²·K)
- Cavity 1 radiative conductance
- 0.236 W/(m²·K)
Formula trace in SI
Gas and radiation
hgap = Nu·k/d + σεeff(T₁ + T₂)(T₁² + T₂²)
Gap 1: 1.177 conductive × Nu 1.335 + 0.236 radiative W/(m²·K).
Center and edge heat flow
Uc = 1/ΣR; Uglass+edge = Uc + ΨP/A
ΣR = 0.735 m²·K/W, edge addition 0.097 W/(m²·K).
Solar gain
SHGC = τsolar + αsolar·Rout/Rtotal
Inward absorbed fraction 5.85 %, SHGC 0.496.
Condensation margin
Tsi = Ti − q/hin; ΔTdew = Tsi − Tdp
Magnus dew point 10.175 °C, surface 15.172 °C, margin 4.997 K.