Substation Ground Grid Calculator
Ground resistance, ground potential rise and step / touch screening for a buried rectangular grid.
Mesh or step limit exceeded. Compared with the selected IEEE 80 exposure limits. GPR exceeds the touch reference. Check local and transferred potentials.
- Sverak resistance
- 1.0811 Ω
- Ground potential rise
- 5,448.7 V
- Corner mesh voltage
- 1,009.1 V
- Corner step voltage
- 587.56 V
Inputs
| Grid length | 80 m |
|---|---|
| Grid width | 60 m |
| Maximum mesh pitch | 10 m |
| Burial depth | 0.5 m |
| Conductor diameter | 12 mm |
| Total rod length | 72 m |
| Rod placement | Corners / perimeter |
| Individual rod length | 3 m |
| Symmetrical ground fault | 8 kA |
| Current split factor | 0.6 × |
| Decrement factor | 1.05 × |
| Native soil resistivity | 150 Ω·m |
| Surface layer thickness | 100 mm |
| Surface material resistivity | 2,500 Ω·m |
| Body weight model | 50 kg / 110 lb |
| Shock / clearing duration | 0.5 s |
Derived values
| Laurent–Niemann estimate | 1.0874 Ω |
|---|---|
| Circular plate reference | 0.95937 Ω |
| Maximum earth current Iɢ | 5.04 kA |
| Grid area | 4,800 m² |
| Horizontal / total buried length | 1,100 m / 1,172 m |
| Mesh bay count | 8 × 6 |
| Fitted pitches | 10 m × 10 m |
| Kₘ / Kᵢ / Kₛ | 0.894 / 1.813 / 0.3799 |
| Mesh / step effective length | 1,214 m / 886.2 m |
| Touch / step voltage limits | 599.8 V / 1,907 V |
Uniform soil and a rectangular, regularly spaced mesh are assumed. Verify current split, transfer paths, actual rod positions and worst-case surface potentials in a site-specific study.