Sparse fin spacing for dusty air
A dusty installation selects wider fin spacing for cleaning and has a measured air volume flow.
Finned tube and air path
ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan
- Fin efficiency
- 88.873%
- Surface eff.
- 89.984%
- Area ratio
- 9.0153
- Shaft power
- 2.0212kW
- Within the displayed screening checks.
Inputs
Calculated results
- Fin efficiency
- 88.873 %
- Overall surface efficiency
- 89.984 %
- Total / bare tube area
- 9.0153
- Fan shaft power
- 2.0212 kW
- Required air mass flow
- 13.456 kg/s
- Required air volume flow
- 11.6 m³/s
- Air temperature rise
- 17.73 K
- Complete fins
- 111,800
- Total airside area
- 643.42 m²
- Reference bare tube area
- 71.37 m²
- Efficiency-weighted area
- 578.97 m²
- Shaft power budget
- 2.6 kW
- Shaft power headroom
- 22.261 %
Worked solution
Preset calculation · Metric SI
- Count 111,800 complete fins across the tube bundle. The exposed and finned surfaces total 643.42 m².
- Apply 88.873 % fin efficiency to the fin area. The area-weighted result is 89.984 % surface efficiency.
- The air heat balance requires 11.6 m³/s. Multiply that flow by the entered pressure drop and divide by efficiency to get 2.0212 kW shaft power.
Use the measured airflow to predict its temperature rise. Set fin density to zero to get the bare tube reference.
Calculation basis
Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.
Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.
Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.
Methodology and references