HeatExchangerLab

Sparse fin spacing for dusty air

A dusty installation selects wider fin spacing for cleaning and has a measured air volume flow.

Finned tube and air path

ηₒ = 1 − (Af/At)(1 − ηf) · Pshaft = V̇air × ΔPair / ηfan

Edit inputs ↓
Fin efficiency
88.873%
Surface eff.
89.984%
Area ratio
9.0153
Shaft power
2.0212kW
Finned tube and air pathFIN SECTIONAIR PATH →Annular discFan at design flow0Shaft budget150% load
The plate or disc shape, tube radius, and fin density drive the cutaway. The bar compares required shaft power to the entered budget.
  • Within the displayed screening checks.

Inputs

mm
mm
mm
fins/cm
m
W/(m·K)
W/(m²·K)
kW
m³/s
kJ/(kg·K)
kg/m³
kPa
%
kW

Calculated results

Fin efficiency
88.873 %
Overall surface efficiency
89.984 %
Total / bare tube area
9.0153
Fan shaft power
2.0212 kW
Required air mass flow
13.456 kg/s
Required air volume flow
11.6 m³/s
Air temperature rise
17.73 K
Complete fins
111,800
Total airside area
643.42 m²
Reference bare tube area
71.37 m²
Efficiency-weighted area
578.97 m²
Shaft power budget
2.6 kW
Shaft power headroom
22.261 %

Worked solution

Preset calculation · Metric SI

  1. Count 111,800 complete fins across the tube bundle. The exposed and finned surfaces total 643.42 m².
  2. Apply 88.873 % fin efficiency to the fin area. The area-weighted result is 89.984 % surface efficiency.
  3. The air heat balance requires 11.6 m³/s. Multiply that flow by the entered pressure drop and divide by efficiency to get 2.0212 kW shaft power.

Use the measured airflow to predict its temperature rise. Set fin density to zero to get the bare tube reference.

Calculation basis

Annular discs use the Schmidt corrected-radius approximation. Rectangular plates use a square outer boundary and a straight-fin efficiency approximation with a corrected tip length.

Total outside area includes both fin faces, exposed fin edges, and the tube area left between fins. ηₒ weights the fin and bare areas at a common airside film coefficient.

Enter an allowable air temperature rise to size the airflow, or use known airflow to predict the rise. Shaft power uses the total air-path pressure drop and fan efficiency. Motor input would also require motor and drive efficiencies.

Methodology and references