HeatExchangerLab

Plate heat exchanger count, velocity & shear

Size a gasketed plate pack and screen channel velocity, wall shear, and pressure drop at the entered flow.

Chevron plate pack

Nactive ≥ Q / (U × ΔT × Aplate) · τw = fᴅρv²/8

Edit inputs ↓
Plate count
67
Channel speed
0.75054m/s
Wall shear
58.464Pa
Plate ΔP
48.284kPa
Chevron plate packCORRUGATED PLATESCHANNEL SECTION45° chevronShear 58.464 Pa3.4 mm gap050 Pa screen100 Pa+
Chevron angle changes the ribs. The channel gap is enlarged. The shear bar uses a 50 Pa screen and caps at 100 Pa. The channel label shows the calculated shear.
  • Within the displayed screening checks.

Inputs

kW
W/(m²·K)
K
m
m
mm
L/min
kg/m³
mPa·s

Calculated results

Installed plates
67
Channel velocity
0.75054 m/s
Average wall shear
58.464 Pa
Core pressure drop
48.284 kPa
Active thermal plates
65
Channels per side per pass
33
Hydraulic diameter
5.812 mm
Channel Reynolds number
4,927.2
Required transfer area
34.3 m²
Area per active plate
0.53352 m²
Installed transfer area
34.679 m²
Darcy friction factor
0.8353

Calculation basis

Use active plate width and length, excluding the port area. Corrugation enlargement multiplies projected plate area. The pack includes two non-transfer end plates and rounds up to equal channels per side and pass.

The hydraulics are for the entered stream. Hydraulic diameter is 2b/φ. A Martin chevron friction factor estimates core pressure drop and average wall shear. Port and multi-pass turning losses are omitted.

Wall shear over 50 Pa is an illustrative antifouling screen. Use supplier predictions and fluid-specific deposition data for final selection.