Heat exchanger effectiveness–NTU rating
Predict duty and outlet temperatures from inlet conditions, heat capacity rates, and known UA.
Effectiveness curve
NTU = UA / Cₘᵢₙ · Q = ε × Cₘᵢₙ × (Tₕ,ᵢ − T𝒸,ᵢ)
- Effectiveness
- 53.893%
- Heat duty
- 1,008.9kW
- Hot outlet
- 81.945°C
- Cold outlet
- 76.042°C
- Within the displayed screening checks.
Inputs
Calculated results
- Effectiveness
- 53.893 %
- Actual heat duty
- 1,008.9 kW
- Hot outlet
- 81.945 °C
- Cold outlet
- 76.042 °C
- Number of transfer units
- 1.0313
- Capacity ratio Cᵣ
- 0.7619
- Minimum capacity rate
- 16 kW/K
- Maximum possible duty
- 1,872 kW
- Difference from ideal duty
- 863.12 kW
Calculation basis
Heat capacity rate is mass flow times specific heat. The smaller rate defines Cₘᵢₙ and the inlet temperature difference sets the maximum possible heat duty.
Closed-form effectiveness relations cover parallel, counterflow, one shell pass, fully mixed crossflow, and either mixed side. Both-unmixed crossflow evaluates the exact single-pass analytical series to numerical precision.
Select a hot or cold isothermal side for phase change. The other stream sets Cₘᵢₙ, so Cᵣ = 0 and ε = 1 − exp(−NTU). The isothermal outlet equals its inlet.
Methodology and references