Plate heat exchanger count, velocity & shear
Size a gasketed plate pack and screen channel velocity, wall shear, and pressure drop at the entered flow.
Chevron plate pack
Nactive ≥ Q / (U × ΔT × Aplate) · τw = fᴅρv²/8
- Plate count
- 67
- Channel speed
- 0.75054m/s
- Wall shear
- 58.464Pa
- Plate ΔP
- 48.284kPa
- Within the displayed screening checks.
Inputs
Calculated results
- Installed plates
- 67
- Channel velocity
- 0.75054 m/s
- Average wall shear
- 58.464 Pa
- Core pressure drop
- 48.284 kPa
- Active thermal plates
- 65
- Channels per side per pass
- 33
- Hydraulic diameter
- 5.812 mm
- Channel Reynolds number
- 4,927.2
- Required transfer area
- 34.3 m²
- Area per active plate
- 0.53352 m²
- Installed transfer area
- 34.679 m²
- Darcy friction factor
- 0.8353
Calculation basis
Use active plate width and length, excluding the port area. Corrugation enlargement multiplies projected plate area. The pack includes two non-transfer end plates and rounds up to equal channels per side and pass.
The hydraulics are for the entered stream. Hydraulic diameter is 2b/φ. A Martin chevron friction factor estimates core pressure drop and average wall shear. Port and multi-pass turning losses are omitted.
Wall shear over 50 Pa is an illustrative antifouling screen. Use supplier predictions and fluid-specific deposition data for final selection.