HeatExchangerLab

Soft-chevron industrial water recovery

A large circulating-water recovery skid uses a 30° plate pattern to manage pump head.

Chevron plate pack

Nactive ≥ Q / (U × ΔT × Aplate) · τw = fᴅρv²/8

Edit inputs ↓
Plate count
51
Channel speed
0.77475m/s
Wall shear
30.061Pa
Plate ΔP
24.665kPa
Chevron plate packCORRUGATED PLATESCHANNEL SECTION30° chevronShear 30.061 Pa4.1 mm gap050 Pa screen100 Pa+
Chevron angle changes the ribs. The channel gap is enlarged. The shear bar uses a 50 Pa screen and caps at 100 Pa. The channel label shows the calculated shear.
  • Average wall shear does not exceed the 50 Pa antifouling screen.

Inputs

kW
W/(m²·K)
K
m
m
mm
L/min
kg/m³
mPa·s

Calculated results

Installed plates
51
Channel velocity
0.77475 m/s
Average wall shear
30.061 Pa
Core pressure drop
24.665 kPa
Active thermal plates
49
Channels per side per pass
25
Hydraulic diameter
7.069 mm
Channel Reynolds number
8,571.4
Required transfer area
55.963 m²
Area per active plate
1.1438 m²
Installed transfer area
56.044 m²
Darcy friction factor
0.40635

Worked solution

Preset calculation · Metric SI

  1. Divide target duty by service U times corrected mean ΔT. The required transfer area is 55.963 m².
  2. Each active plate contributes 1.1438 m². The balanced pack uses 51 plates including the two end plates.
  3. Use 25 channels per side per pass to find velocity. The chevron model gives 30.061 Pa wall shear and 24.665 kPa core loss.

Switch to 60° with fixed U to isolate the pressure and wall-shear effects of chevron angle.

Calculation basis

Use active plate width and length, excluding the port area. Corrugation enlargement multiplies projected plate area. The pack includes two non-transfer end plates and rounds up to equal channels per side and pass.

The hydraulics are for the entered stream. Hydraulic diameter is 2b/φ. A Martin chevron friction factor estimates core pressure drop and average wall shear. Port and multi-pass turning losses are omitted.

Wall shear over 50 Pa is an illustrative antifouling screen. Use supplier predictions and fluid-specific deposition data for final selection.