Two-pass glycol heat recovery
A two-pass plate pack recovers heat into a glycol circuit at a modest terminal drive.
Chevron plate pack
Nactive ≥ Q / (U × ΔT × Aplate) · τw = fᴅρv²/8
- Plate count
- 49
- Channel speed
- 1.1892m/s
- Wall shear
- 161.28Pa
- Plate ΔP
- 234.33kPa
- Within the displayed screening checks.
Inputs
Calculated results
- Installed plates
- 49
- Channel velocity
- 1.1892 m/s
- Average wall shear
- 161.28 Pa
- Core pressure drop
- 234.33 kPa
- Active thermal plates
- 47
- Channels per side per pass
- 12
- Hydraulic diameter
- 7.2131 mm
- Channel Reynolds number
- 2,124.1
- Required transfer area
- 31.238 m²
- Area per active plate
- 0.68723 m²
- Installed transfer area
- 32.3 m²
- Darcy friction factor
- 0.87726
Worked solution
Preset calculation · Metric SI
- Divide target duty by service U times corrected mean ΔT. The required transfer area is 31.238 m².
- Each active plate contributes 0.68723 m². The balanced pack uses 49 plates including the two end plates.
- Use 12 channels per side per pass to find velocity. The chevron model gives 161.28 Pa wall shear and 234.33 kPa core loss.
Confirm that each side has an integer number of channels per pass. Check core pressure drop separately from port losses.
Calculation basis
Use active plate width and length, excluding the port area. Corrugation enlargement multiplies projected plate area. The pack includes two non-transfer end plates and rounds up to equal channels per side and pass.
The hydraulics are for the entered stream. Hydraulic diameter is 2b/φ. A Martin chevron friction factor estimates core pressure drop and average wall shear. Port and multi-pass turning losses are omitted.
Wall shear over 50 Pa is an illustrative antifouling screen. Use supplier predictions and fluid-specific deposition data for final selection.