High-chevron pack for a wall shear check
The design uses narrow 60° channels to raise velocity and shear in a fouling-sensitive liquid service.
Chevron plate pack
Nactive ≥ Q / (U × ΔT × Aplate) · τw = fᴅρv²/8
- Plate count
- 53
- Channel speed
- 1.7258m/s
- Wall shear
- 660.08Pa
- Plate ΔP
- 637.92kPa
- Within the displayed screening checks.
Inputs
Calculated results
- Installed plates
- 53
- Channel velocity
- 1.7258 m/s
- Average wall shear
- 660.08 Pa
- Core pressure drop
- 637.92 kPa
- Active thermal plates
- 51
- Channels per side per pass
- 26
- Hydraulic diameter
- 4.5528 mm
- Channel Reynolds number
- 7,107.4
- Required transfer area
- 26.638 m²
- Area per active plate
- 0.52767 m²
- Installed transfer area
- 26.911 m²
- Darcy friction factor
- 1.7818
Worked solution
Preset calculation · Metric SI
- Divide target duty by service U times corrected mean ΔT. The required transfer area is 26.638 m².
- Each active plate contributes 0.52767 m². The balanced pack uses 53 plates including the two end plates.
- Use 26 channels per side per pass to find velocity. The chevron model gives 660.08 Pa wall shear and 637.92 kPa core loss.
Compare the shear marker with 50 Pa and check the associated core pressure drop before increasing pass count.
Calculation basis
Use active plate width and length, excluding the port area. Corrugation enlargement multiplies projected plate area. The pack includes two non-transfer end plates and rounds up to equal channels per side and pass.
The hydraulics are for the entered stream. Hydraulic diameter is 2b/φ. A Martin chevron friction factor estimates core pressure drop and average wall shear. Port and multi-pass turning losses are omitted.
Wall shear over 50 Pa is an illustrative antifouling screen. Use supplier predictions and fluid-specific deposition data for final selection.
Methodology and references