HeatExchangerLab

Two-pass glycol heat recovery

A two-pass plate pack recovers heat into a glycol circuit at a modest terminal drive.

Chevron plate pack

Nactive ≥ Q / (U × ΔT × Aplate) · τw = fᴅρv²/8

Edit inputs ↓
Plate count
49
Channel speed
1.1892m/s
Wall shear
161.28Pa
Plate ΔP
234.33kPa
Chevron plate packCORRUGATED PLATESCHANNEL SECTION45° chevronShear 161.28 Pa4.4 mm gap050 Pa screen100 Pa+
Chevron angle changes the ribs. The channel gap is enlarged. The shear bar uses a 50 Pa screen and caps at 100 Pa. The channel label shows the calculated shear.
  • Within the displayed screening checks.

Inputs

kW
W/(m²·K)
K
m
m
mm
L/min
kg/m³
mPa·s

Calculated results

Installed plates
49
Channel velocity
1.1892 m/s
Average wall shear
161.28 Pa
Core pressure drop
234.33 kPa
Active thermal plates
47
Channels per side per pass
12
Hydraulic diameter
7.2131 mm
Channel Reynolds number
2,124.1
Required transfer area
31.238 m²
Area per active plate
0.68723 m²
Installed transfer area
32.3 m²
Darcy friction factor
0.87726

Worked solution

Preset calculation · Metric SI

  1. Divide target duty by service U times corrected mean ΔT. The required transfer area is 31.238 m².
  2. Each active plate contributes 0.68723 m². The balanced pack uses 49 plates including the two end plates.
  3. Use 12 channels per side per pass to find velocity. The chevron model gives 161.28 Pa wall shear and 234.33 kPa core loss.

Confirm that each side has an integer number of channels per pass. Check core pressure drop separately from port losses.

Calculation basis

Use active plate width and length, excluding the port area. Corrugation enlargement multiplies projected plate area. The pack includes two non-transfer end plates and rounds up to equal channels per side and pass.

The hydraulics are for the entered stream. Hydraulic diameter is 2b/φ. A Martin chevron friction factor estimates core pressure drop and average wall shear. Port and multi-pass turning losses are omitted.

Wall shear over 50 Pa is an illustrative antifouling screen. Use supplier predictions and fluid-specific deposition data for final selection.

Methodology and references