One-minute ventilation for a 12×20 ft greenhouse
For an initial summer ventilation check, approximate the greenhouse as 12×20 ft with an average air height of 8 ft. Use no duct or filter allowance for the direct exhaust baseline.
Inputs
Results
Estimated free-air rating
60 air changes/hour · 100% modeled airflow retained
- Room volume
- 1,920 ft³
- Room volume
- 54.37 m³
- Target delivered airflow
- 1,920 CFM
- Target delivered airflow
- 3,262.1 m³/h
- Estimated free-air rating
- 1,920 CFM
- Estimated free-air rating
- 3,262.1 m³/h
Delivered flow and fan rating
Compare required delivery with the estimated no-restriction rating.
Inputs used
- Interior length
- 20 ft
- Interior width
- 12 ft
- Interior height
- 8 ft
- Time per air exchange
- 1 min
- Carbon filter loss
- 0 %
- Straight duct run
- 0 ft
- Duct loss per reference length
- 5 % / 10 ft
- 90° elbows
- 0
- Loss per elbow
- 5 %
Worked calculation
- Measure interior air volume
20 ft × 12 ft × 8 ft = 1,920 ft³
- Find the delivered airflow needed
1,920 ft³ ÷ 1 min = 1,920 CFM
- Multiply retained fractions
1 filter × 1 duct × 1 elbows = 100% retained
- Find the estimated free-air rating
1,920 CFM ÷ 1 = 1,920 CFM (3,262.1 m³/h)
What the example shows
Volume divided by one minute gives 1,920 CFM delivered. Include the installed louver, screen and intake resistance when evaluating equipment.
How the model works
Filter, duct and elbow inputs are planning allowances. Duct loss compounds over each 10 ft equivalent, and elbow loss compounds for each fitting. Pressure drop depends on airflow, duct diameter, filter loading and fitting geometry.
Select a fan using its CFM at the operating static pressure for your system. Use the estimated free-air rating as a screening number. Check intake area, ventilation demand from heat and moisture, and the installed fan curve.
References
Common questions
Which height belongs in a sloped 12×20 greenhouse volume estimate?
Use the volume-equivalent average height. A gable with uniform cross-section averages the eave and ridge heights.
Can I split 1,920 CFM between multiple fans?
Yes, assess the fans’ combined delivered airflow at their installed pressure. Check intake distribution and whether control stages cover the expected load.