5×5 tent fan airflow with a long duct and three elbows

A 175 ft³ tent exhausts through 20 ft of duct, three right-angle bends and a carbon filter. The target is an exchange every 1.5 minutes.

Inputs

Room size and ventilation
ft
ft
ft
min
Airflow resistance allowances
%
ft
% / 10 ft
%

Results

Estimated free-air rating

188.5 CFM

40 air changes/hour · 61.9% modeled airflow retained

Room volume
175 ft³
Room volume
4.96 m³
Target delivered airflow
116.7 CFM
Target delivered airflow
198.2 m³/h
Estimated free-air rating
188.5 CFM
Estimated free-air rating
320.2 m³/h

Delivered flow and fan rating

Compare required delivery with the estimated no-restriction rating.

Exhaust fan airflow comparisonDelivered airflow: 116.67 CFM. Estimated free-air rating: 188.47 CFMDelivered airflow116.7 CFMEstimated free-air rating188.5 CFM

Worked calculation

  1. Measure interior air volume

    5 ft × 5 ft × 7 ft = 175 ft³

  2. Find the delivered airflow needed

    175 ft³ ÷ 1.5 min = 116.67 CFM

  3. Multiply retained fractions

    0.8 filter × 0.9025 duct × 0.85737 elbows = 61.9% retained

  4. Find the estimated free-air rating

    116.67 CFM ÷ 0.61902 = 188.47 CFM (320.2 m³/h)

What the example shows

The 116.7 CFM delivered target increases to an estimated 188.5 CFM free air with the entered losses. Shortening the duct or improving fittings changes the estimate.

How the model works

Filter, duct and elbow inputs are planning allowances. Duct loss compounds over each 10 ft equivalent, and elbow loss compounds for each fitting. Pressure drop depends on airflow, duct diameter, filter loading and fitting geometry.

Select a fan using its CFM at the operating static pressure for your system. Use the estimated free-air rating as a screening number. Check intake area, ventilation demand from heat and moisture, and the installed fan curve.

References

Common questions

How do three right-angle bends affect the 5×5 fan estimate?

Each bend applies its retained fraction. At 5% per bend, the three together retain about 85.7% before the duct and filter allowances.

Why measure the straight run separately from fittings?

The model applies one length allowance and a separate bend allowance. Entering an equivalent length for the bends as well would double count them here.