5×5 tent fan airflow with a long duct and three elbows
A 175 ft³ tent exhausts through 20 ft of duct, three right-angle bends and a carbon filter. The target is an exchange every 1.5 minutes.
Inputs
Results
Estimated free-air rating
40 air changes/hour · 61.9% modeled airflow retained
- Room volume
- 175 ft³
- Room volume
- 4.96 m³
- Target delivered airflow
- 116.7 CFM
- Target delivered airflow
- 198.2 m³/h
- Estimated free-air rating
- 188.5 CFM
- Estimated free-air rating
- 320.2 m³/h
Delivered flow and fan rating
Compare required delivery with the estimated no-restriction rating.
Inputs used
- Interior length
- 5 ft
- Interior width
- 5 ft
- Interior height
- 7 ft
- Time per air exchange
- 1.5 min
- Carbon filter loss
- 20 %
- Straight duct run
- 20 ft
- Duct loss per reference length
- 5 % / 10 ft
- 90° elbows
- 3
- Loss per elbow
- 5 %
Worked calculation
- Measure interior air volume
5 ft × 5 ft × 7 ft = 175 ft³
- Find the delivered airflow needed
175 ft³ ÷ 1.5 min = 116.67 CFM
- Multiply retained fractions
0.8 filter × 0.9025 duct × 0.85737 elbows = 61.9% retained
- Find the estimated free-air rating
116.67 CFM ÷ 0.61902 = 188.47 CFM (320.2 m³/h)
What the example shows
The 116.7 CFM delivered target increases to an estimated 188.5 CFM free air with the entered losses. Shortening the duct or improving fittings changes the estimate.
How the model works
Filter, duct and elbow inputs are planning allowances. Duct loss compounds over each 10 ft equivalent, and elbow loss compounds for each fitting. Pressure drop depends on airflow, duct diameter, filter loading and fitting geometry.
Select a fan using its CFM at the operating static pressure for your system. Use the estimated free-air rating as a screening number. Check intake area, ventilation demand from heat and moisture, and the installed fan curve.
References
Common questions
How do three right-angle bends affect the 5×5 fan estimate?
Each bend applies its retained fraction. At 5% per bend, the three together retain about 85.7% before the duct and filter allowances.
Why measure the straight run separately from fittings?
The model applies one length allowance and a separate bend allowance. Entering an equivalent length for the bends as well would double count them here.