Two-minute air exchange for a 2×4 grow tent

The interior measures 2×4×6 ft. It uses four feet of duct and one 90° elbow, and no filter is installed.

Inputs

Room size and ventilation
ft
ft
ft
min
Airflow resistance allowances
%
ft
% / 10 ft
%

Results

Estimated free-air rating

25.8 CFM

30 air changes/hour · 93.1% modeled airflow retained

Room volume
48 ft³
Room volume
1.36 m³
Target delivered airflow
24 CFM
Target delivered airflow
40.8 m³/h
Estimated free-air rating
25.8 CFM
Estimated free-air rating
43.8 m³/h

Delivered flow and fan rating

Compare required delivery with the estimated no-restriction rating.

Exhaust fan airflow comparisonDelivered airflow: 24 CFM. Estimated free-air rating: 25.79 CFMDelivered airflow24 CFMEstimated free-air rating25.8 CFM

Worked calculation

  1. Measure interior air volume

    2 ft × 4 ft × 6 ft = 48 ft³

  2. Find the delivered airflow needed

    48 ft³ ÷ 2 min = 24 CFM

  3. Multiply retained fractions

    1 filter × 0.97969 duct × 0.95 elbows = 93.07% retained

  4. Find the estimated free-air rating

    24 CFM ÷ 0.93071 = 25.79 CFM (43.8 m³/h)

What the example shows

A two-minute exchange needs about 24 CFM delivered. The modeled short duct and elbow raise the free-air estimate to approximately 25.8 CFM.

How the model works

Filter, duct and elbow inputs are planning allowances. Duct loss compounds over each 10 ft equivalent, and elbow loss compounds for each fitting. Pressure drop depends on airflow, duct diameter, filter loading and fitting geometry.

Select a fan using its CFM at the operating static pressure for your system. Use the estimated free-air rating as a screening number. Check intake area, ventilation demand from heat and moisture, and the installed fan curve.

References

Common questions

Can I use the same 24 CFM if the 2×4 tent adds a carbon filter?

Keep 24 CFM as the delivered target and increase modeled resistance to reflect the new filter. Verify its pressure drop at the intended flow.

How do I include a small duct length like four feet?

Enter the measured straight run. The model applies a fraction of the per-10-foot duct allowance for shorter lengths.