Metric greenhouse exhaust for a 3 × 2.4 × 2.2 m room

A propagation room of 15.84 m³ targets one exchange every two minutes. Enter a 30% filter allowance, five meters of duct and two bends.

Inputs

Room size and ventilation
m
m
m
min
Airflow resistance allowances
%
m
% / m
%

Results

Estimated free-air rating

835.7 m³/h

30 air changes/hour · 56.9% modeled airflow retained

Room volume
559.38 ft³
Room volume
15.84 m³
Target delivered airflow
279.7 CFM
Target delivered airflow
475.2 m³/h
Estimated free-air rating
491.9 CFM
Estimated free-air rating
835.7 m³/h

Delivered flow and fan rating

Compare required delivery with the estimated no-restriction rating.

Exhaust fan airflow comparisonDelivered airflow: 475.2 m³/h. Estimated free-air rating: 835.73 m³/hDelivered airflow475.2 m³/hEstimated free-air rating835.7 m³/h

Worked calculation

  1. Measure interior air volume

    3 m × 2.4 m × 2.2 m = 559.38 ft³

  2. Find the delivered airflow needed

    559.38 ft³ ÷ 2 min = 279.69 CFM

  3. Multiply retained fractions

    0.7 filter × 0.9193 duct × 0.8836 elbows = 56.86% retained

  4. Find the estimated free-air rating

    279.69 CFM ÷ 0.56861 = 491.89 CFM (835.7 m³/h)

What the example shows

The room needs 475.2 m³/h delivered. At the entered resistance allowances the free-air screening size is about 836 m³/h.

How the model works

Filter, duct and elbow inputs are planning allowances. Duct loss compounds over each 10 ft equivalent, and elbow loss compounds for each fitting. Pressure drop depends on airflow, duct diameter, filter loading and fitting geometry.

Select a fan using its CFM at the operating static pressure for your system. Use the estimated free-air rating as a screening number. Check intake area, ventilation demand from heat and moisture, and the installed fan curve.

References

Common questions

How do I convert a two-minute exchange into cubic meters per hour?

Two minutes per exchange is 30 exchanges per hour. Multiply 30 by 15.84 m³ to get 475.2 m³/h delivered.

Why does the metric duct label use loss per meter?

It converts the same duct-loss reference from percent per 10 feet to percent per meter. Changing display units preserves the modeled restriction.